modelLiangAndZhuCalibrated

Measured velocities based on Liang et al. 2020 calibrated on own heat pump

Extends from AixLib.Fluid.HeatPumps.ModularReversible.RefrigerantCycle.Frosting.BaseClasses.PartialVelocityBased.

Information

This model calibrates the growth velocities from Liang et al., who base their work on the zones from Zhu et al., onto dynamic frost densities and a custom build heat pump at the Institute for Energy Efficient Buildings and Indoor Climate.

The calibration was performed and used for Römer et al. In addition to Liang et al., a time-delay after the last defrost is used before the frost starts to grow again. This was added based observed data from dynamic tests and is grounded in the fact that fins are warm after defrost, and, thus, don't directly accumulate frost.

For more information, see the base-model: AixLib.Fluid.HeatPumps.ModularReversible.RefrigerantCycle.Frosting.BaseClasses.PartialVelocityBased .

References

Römer, Fabian and Fuchs, Nico and Fuchs, Nico and Müller, Dirk, Practical, Near-Optimal Design Rule Extraction for Heat Pumps in Single-Family Buildings (September 03, 2025). Available at SSRN: https://ssrn.com/abstract=5633891

J.H. Zhu, Y.Y. Sun, W. Wang, S.M. Deng, Y.J. Ge, and L.T. Li. Developing a new frosting map to guide defrosting control for air-source heat pump units. Applied Thermal Engineering, November 2015 doi:10.1016/j.applthermaleng.2015.06.076.

Liang, S., Wang, W., Sun, Y., Li, Z., Zhao, J., Lin, Y., and Deng, S. (2020). A novel characteristic index for frosting suppression based on the configuration and operation of air source heat pumps. International Journal of Refrigeration, 109, 161-171. https://doi.org/10.1016/j.ijrefrig.2019.10.009.

Parameters

TypeNameDefaultDescription
RealtimeMiltimeSev*facSevMil
RealdefrostEfficiency0.65Defrost efficiency
RealfacSevMil1.358403
RealtimeSev1083.524850
RealcorCoeffSev0.231588Correction coefficient for severe zone
RealcorCoeffMod0.218708Correction coefficient for moderate zone
RealcorCoeffMil0.218708Correction coefficient for mild zone

Components

TypeNameDefaultDescription
AixLib.Fluid.HeatPumps.ModularReversible.RefrigerantCycle.Frosting.BaseClasses.ZhuFrostingZonezhuFroZonCurrent frosting zone
Modelica.Blocks.Sources.RealExpressiontimeFirstFroTime of first frost after last defrost
Modelica.Blocks.Logical.TimertimeOnTime device is on since last defrost

Revisions

  • December 22, 2025 by Fabian Roemer:
    First implementation (see issue AixLib #1623)