modelCase600
Extends from AixLib.ThermalZones.HighOrder.Validation.ASHRAE140.BaseClasses.PartialCase.
Information
Input Specifications of Case 600 as described in ASHRAE Standard 140:
- Low mass building
- 12 m2 south-facing window area
- Air exchange rate: 0.41
- Thermostat control:
Heat = ON IF Temp < 20°C otherwise Heat=OFF
Cool = ON IF Temp > 27°C otherwise Cool = OFF - Internal gains: 200 W
- Solar absorptance:
exterior: 0.6
interior: 0.6 - Infrared emittance:
exterior: 0.9
interior: 0.9
All following ASHRAE140 test cases are based on Case600.
References
- ASHRAE140-2017
Components
| Type | Name | Default | Description |
|---|---|---|---|
| Utilities.Sources.HeaterCooler.HeaterCoolerPI | idealHeaterCooler | ||
| Modelica.Blocks.Sources.Constant | AirExchangeRate | ||
| Modelica.Blocks.Sources.Constant | Tset_Cooler | ||
| Modelica.Blocks.Sources.Constant | TSet_Heater | ||
| Modelica.Blocks.Math.UnitConversions.From_degC | from_degC | ||
| Modelica.Blocks.Math.UnitConversions.From_degC | from_degC1 |