modelCase950

Extends from AixLib.ThermalZones.HighOrder.Validation.ASHRAE140.Case650.

Information

Input Specifications of Case 950 as described in ASHRAE Standard 140:

Difference to case 600:

  • Air exchange rate: 10.8
  • 18-7 h: Vent fan = ON
  • 7-18 h: Vent fan = OFF
  • Heating = always OFF
  • 18-7 h: Cool = OFF
  • 7-18 h: Cool =ON IF Temp < 27°C, otherwise Cool=OFF