modelCase650

Extends from AixLib.ThermalZones.ISO13790.Validation.BESTEST.Cases6xx.Case600.

Information

This model is used for the test case 650 of the BESTEST validation suite. Case650 is the same as Case600, but with the following modifications:

  • From 18h00 hours to 07h00 hours, vent fan = on
  • From 07h00 hours to 18h00 hours, vent fan = off
  • Heating is always off
  • From 07h00 hours to 18h00 hours, cooling is on if zone temperature > 27°C, otherwise cool = off.
  • From 18h00 hours to 07h00 hours, cooling is always off.
  • Ventilation fan capacity is 1700 standard m3/h (in addition to specified infiltration rate). After adjustment for the altitude, the capacity is 1409 m3/h.
  • No waste heat from fan.

Components

TypeNameDefaultDescription
AixLib.Fluid.Sensors.DensitysenDen
Modelica.Blocks.Math.Productproduct1Product to compute infiltration mass flow rate
Modelica.Blocks.Sources.CombiTimeTableventVentilation air flow rate
AixLib.Fluid.Sources.MassFlowSource_TsinInfSink model for air infiltration
AixLib.Fluid.Sources.Outsideout

Revisions

  • Mar 2, 2024, by Alessandro Maccarini:
    First implementation.