modelCase950
Extends from AixLib.ThermalZones.ISO13790.Validation.BESTEST.Cases9xx.Case900.
Information
This model is used for the test case 950 of the BESTEST validation suite. Case950 is the same as Case900, but with the following modifications:
- From 18h00 hours to 07h00 hours, vent fan = on
- From 07h00 hours to 18h00 hours, vent fan = off
- Heating is always off
- From 07h00 hours to 18h00 hours, cooling is on if zone temperature > 27°C, otherwise cool = off.
- From 18h00 hours to 07h00 hours, cooling is always off.
- Ventilation fan capacity is 1700 standard m3/h (in addition to specified infiltration rate). After adjustment for the altitude, the capacity is 1409 m3/h.
- No waste heat from fan.
Components
| Type | Name | Default | Description |
|---|---|---|---|
| AixLib.Fluid.Sources.MassFlowSource_T | sinInf | Sink model for air infiltration | |
| Modelica.Blocks.Math.Product | product1 | Product to compute infiltration mass flow rate | |
| Modelica.Blocks.Sources.CombiTimeTable | vent | Ventilation air flow rate | |
| AixLib.Fluid.Sensors.Density | senDen | ||
| AixLib.Fluid.Sources.Outside | out |
Revisions
-
Mar 2, 2024, by Alessandro Maccarini:
First implementation.