modelHeatConvOutside
Model for heat transfer at outside surfaces. Choice between multiple models
Extends from Modelica.Thermal.HeatTransfer.Interfaces.Element1D.
Information
Overview
The HeatTransferOutside is a model for the convective heat transfer at outside walls
Concept
It allows the choice between three different models:
- after DIN 6946:
h = 4+4v, whereh(hCon) is the heat transfer coefficent andvis the wind speed - after the ASHRAE Fundamentals Handbook from 1989, the way it is
presented in EnergyPlus Engineering reference from 2011:
h = D+Ev+Fv^2, whereh(hCon) andvare as above and the coefficientsD, E, Fdepend on the surface of the outer wall.
Attention: This is a combined coefficient for convective and radiative heat exchange. - with a custom constant
h(hCon) value
References
- DIN 6946 p.20
- ASHRAEHandbook1989, as cited in EnergyPlus Engineering Reference. : EnergyPlus Engineering Reference, 2011 p.56
Example Results
AixLib.Utilities.Examples.HeatTransfer_test
AixLib.Utilities.Examples.HeatConv_outside
-
November 16, 2016 by Ana Constantin:
Conditioned input WindSpeedPort and introduced protected input WindSpeed_internal
-
April 1, 2014 by Ana Constantin:
Uses components from MSL and respects the naming conventions
-
March 30, 2012 by Ana Constantin:
Implemented.
Parameters
| Type | Name | Default | Description |
|---|---|---|---|
| Computational Models | |||
| AixLib.ThermalZones.HighOrder.Components.Types.CalcMethodConvectiveHeatTransfer | calcMethod | AixLib.ThermalZones.HighOrder.Components.Types.CalcMethodConvectiveHeatTransfer.ASHRAE_Fundamentals | Calculation method for convective heat transfer coefficient |
| Surface properties | |||
| Modelica.Units.SI.Area | A | Area of surface | |
| Modelica.Units.SI.CoefficientOfHeatTransfer | hCon_const | 25 | Custom convective heat transfer coeffient |
| DataBase.Surfaces.RoughnessForHT.PolynomialCoefficients_ASHRAEHandbook | surfaceType | DataBase.Surfaces.RoughnessForHT.Brick_RoughPlaster() | Surface type |
Components
| Type | Name | Default | Description |
|---|---|---|---|
| Modelica.Units.SI.CoefficientOfHeatTransfer | hCon | Convection heat transfer coeffient | |
| Modelica.Blocks.Interfaces.RealInput | WindSpeedPort |