modelWaterDesignTemperature

Diagram of WaterDesignTemperature

Information

Hypothesis and equations

On/Off control model for a heat generator, according to the hydraulic circuit temperature.

The number of points of the water design curve has to be chosen based on the need (system output water temperature depending on exterior temperature, 3 temperature points minimum).

Bibliography

none

Instructions for use

none

Known limits / Use precautions

none

Validations

Validated model - Hubert Blervaque, Sila Filfli 02/2013

--------------------------------------------------------------
Licensed by EDF under a 3-clause BSD-license
Copyright © EDF 2009 - 2023
BuildSysPro version 3.6.0
Author : Hubert BLERVAQUE, Sila FILFLI, EDF (2013)
--------------------------------------------------------------

Parameters

TypeNameDefaultDescription
BooleanRegTORtrueOn/Off control ?
Real[:,2]table[-20, 60; -7, 52; 0, 43; 7, 37; 20, 20]Table of water design curve : exterior temperature (°C) in 1st row and system output temperature (°C) in 2nd row
Modelica.Units.SI.TemperatureDifferenceTHyst1Upper and lower tolerance compared with the setpoint

Connectors

TypeNameDefaultDescription
Modelica.Blocks.Interfaces.RealInputT_extExterior temperature (°K)
Modelica.Blocks.Interfaces.BooleanOutputuHeatpump On/Off
Modelica.Blocks.Interfaces.RealInput[2]RetourDEauPoint of the hydraulic network which should respect the water design curve
Modelica.Blocks.Interfaces.RealOutputT_spSetpoint temperature (°K)

Revisions

Hubert Blervaque 09/2013 : Ajout d'une option permetttant d'utilier la régulation tout-ou-rien, sinon les connecteurs associés sont occultés.

Benoît Charrier 05/2015 : Suppression des connecteurs T & m_flow.