modelThreeWayValveAndPump

Three ways valve with water pump
Diagram of ThreeWayValveAndPump

Information

Hypothesis and equations

This model incorporates a 3 way valve and a water pump to distribute hot water coming from a source (boiler, heat pump,..) in two circuits (heating and domestic hot water, DHW).

The valve has only 2 positions : 100% mass flow rate for heating or 100% mass flow rate for DHW.

Several parameters are available for this model:

  • Pe_cons_WP (60W by default) : electric power consumption of water pump;
  • MFR (0.38 kg/s by default) : nominal mass flow rate;
  • MFR_reduction (0.6 by default) : percentage of nominal mass flow rate used for modes when water is not heated (i.e. when water pump is running but the heat pump or the boiler are not in operation)
  • MFR_min (1e-3 by default) : minimal mass flow rate for each circuit (to avoid division by zero downstream the model)


The input "mode" sets either DHW or HEATING and the mass flow rate (NOMINAL or REDUCED):

  • mode : 1 - HEATING CIRCUIT - COMPRESSOR ON  - WP ON NOMINAL MASS FLOW RATE
  • mode : 2 - DHW CIRCUIT     - COMPRESSOR ON  - WP ON NOMINAL MASS FLOW RATE
  • mode : 3 - HEATING CIRCUIT - COMPRESSOR ON  + ELECTRIC DHW BACKUP ON   - WP ON NOMINAL MASS FLOW RATE
  • mode : 4 - DHW CIRCUIT     - COMPRESSOR OFF + ELECTRIC DHW BACKUP ON   - WP OFF NOMINAL MASS FLOW RATE
  • mode : 5 - HEATING CIRCUIT - COMPRESSOR OFF + ELECTRIC HEATING AND DHW BACKUPS ON   - WP ON NOMINAL MASS FLOW RATE
  • mode : 6 - HEATING CIRCUIT - COMPRESSOR OFF + ELECTRIC DHW BACKUP ON   - WP ON NOMINAL MASS FLOW RATE
  • mode : 7 - HEATING CIRCUIT - COMPRESSOR OFF + ELECTRIC DHW BACKUP OFF  - WP ON REDUCED MASS FLOW RATE
  • mode : 8 - DHW CIRCUIT     - COMPRESSOR OFF + ELECTRIC BACKUP OFF  - WP ON REDUCED MASS FLOW RATE
  • mode : 9 - ALL System OFF

Bibliography

none

Instructions for use

none

Known limits / Use precautions

none

Validations

Validated model - Alberto Tejeda 12/2015

--------------------------------------------------------------
Licensed by EDF under a 3-clause BSD-license
Copyright © EDF 2009 - 2023
BuildSysPro version 3.6.0
Author : Alberto TEJEDA, EDF (2015)
--------------------------------------------------------------

Parameters

TypeNameDefaultDescription
Modelica.Units.SI.PowerPe_cons_WP30
Modelica.Units.SI.TimeD30Delay time to switch from one way to other
Modelica.Units.SI.MassFlowRateMFR0.38Water mass flow rate
RealMFR_reduction0.6Percentage of water mass flow rate during compressor off function
Modelica.Units.SI.MassFlowRateMFR_min1e-3Débit minimal du radiateur pour empecher l'arrêt de la simulation

Connectors

TypeNameDefaultDescription
Modelica.Blocks.Interfaces.RealInput[2]port_in_HP1:Temp / 2:m_flow
Modelica.Blocks.Interfaces.RealOutput[2]port_out_HP1:Temp / 2:m_flow
Modelica.Blocks.Interfaces.IntegerInputmode
Modelica.Blocks.Interfaces.RealInput[2]port_in_DHW1:Temp / 2:m_flow
Modelica.Blocks.Interfaces.RealOutput[2]port_out_DHW1:Temp / 2:m_flow
Modelica.Blocks.Interfaces.RealInput[2]port_in_HC1:Temp / 2:m_flow
Modelica.Blocks.Interfaces.RealOutput[2]port_out_HC1:Temp / 2:m_flow
Modelica.Blocks.Interfaces.RealOutputPe_cons

Components

TypeNameDefaultDescription
Realmin_pos_V3V1e-3
Modelica.Units.SI.MassFlowRatem_flow
Modelica.Units.SI.EnergyEe_cons
Realx_V3V
Modelica.Blocks.Continuous.FirstOrderfirstOrder_x_V3V
Modelica.Blocks.Continuous.FirstOrderfirstOrder_m_flow

Revisions

07/2018 - S. Froidurot : Récupération de Pe_cons en output du modèle, correction erreur dans la documentation