modelBasedCharacteristicEquation1

Room temperature based on average between radiative and convective temperatures
Diagram of BasedCharacteristicEquation1

Extends from BuildSysPro.Systems.HVAC.Emission.Radiator.Components.BasedCharacteristicEquation (Partial model for characteristic equation of a radiator (EN442)).

Information

--------------------------------------------------------------
Licensed by EDF under a 3-clause BSD-license
Copyright © EDF 2009 - 2023
BuildSysPro version 3.6.0
Authors : Gilles PLESSIS, Hassan BOUIA EDF (2016)
--------------------------------------------------------------

Parameters

TypeNameDefaultDescription
RealKm (from BasedCharacteristicEquation)Pnom/DTnom^nNomKm coefficient (sometimes refers as KS or UA coefficient) used in the Characteristic equation
EN442 - Nominal point
SI.EnergyFlowRatePnom (from BasedCharacteristicEquation)411Nominal power for a DT=50 K, based on inlet temperature 75/65
SI.TemperatureDifferenceDTnom (from BasedCharacteristicEquation)50Temperature difference (air to water) at nominal operating point
RealnNom (from BasedCharacteristicEquation)1.225Slope at nominal point
RealFracRad (from BasedCharacteristicEquation)0.35Radiative fraction of heat

Connectors

TypeNameDefaultDescription
BaseClasses.HeatTransfer.Interfaces.HeatPort_bRad (from BasedCharacteristicEquation)HeatPort for long wave radiation exchanges
BaseClasses.HeatTransfer.Interfaces.HeatPort_bConv (from BasedCharacteristicEquation)HeatPort for convective heat transfers

Components

TypeNameDefaultDescription
SI.TemperatureT_HWR (from BasedCharacteristicEquation)Temperature of the hot water radiator
SI.EnergyFlowRateQtot (from BasedCharacteristicEquation)Heating power output from the radiator
SI.TemperatureDifferenceDTamArithmetic mean temperature difference for radiation and convection