modelYD

IEEE 4 node test feeder model with balanced load and Y - D connection (step up)

Extends from BuildingSystems.Electrical.AC.ThreePhasesUnbalanced.Validation.IEEETests.Test4NodesFeeder.BaseClasses.IEEE4.

Information

IEEE 4 nodes validation test case with the following characteristics

  • balanced load,
    • power consumption on each phase P1,2,3 = 1800 kW
    • power factor on each phase cosφ1,2,3 = 0.9
  • voltage step-up transformer (VPri=12.47 kV, VSec = 24.9kV),
  • Y-D transformer