modelPartialTwoPortRLC

Partial model of an RLC element that links two electrical connectors

Extends from BuildingSystems.Electrical.Interfaces.PartialTwoPort, Modelica.Electrical.Analog.Interfaces.ConditionalHeatPort.

Information

Partial model of a resistance that links two generalized electrical connectors.

The model computes a resistance R(T) that varies depending on the temperature T as

R(T) = Rref (M + T)/(M + Tref),

where the resistance Rref is the reference value of the resistance, M is the temperature coefficient of the cable material, and Tref is the reference temperature. The temperature T is the temperature of the heat port if useHeatPort = true.

The impedance L and the capacity C do not vary with respect to the temperature and are specified by the user.

Parameters

TypeNameDefaultDescription
Modelica.Units.SI.ResistanceRResistance at temperature T_ref
Modelica.Units.SI.TemperatureT_ref298.15Reference temperature
Modelica.Units.SI.TemperatureM507.65Temperature constant (R_actual = R*(M + T_heatPort)/(M + T_ref))
Modelica.Units.SI.CapacitanceCCapacity
Modelica.Units.SI.InductanceLInductance
Nominal conditions
Modelica.Units.SI.VoltageV_nominalNominal voltage (V_nominal >= 0)

Components

TypeNameDefaultDescription
Modelica.Units.SI.ResistanceR_actualActual resistance = R*(M + T_heatPort)/(M + T_ref)

Revisions

  • June 3, 2014, by Marco Bonvini:
    Added User's guide.