modelTable_m_flow
Mass flow(y-axis) vs Pressure(x-axis) cubic spline fit model based from table data, with last two points linearly interpolated
Extends from Buildings.Airflow.Multizone.BaseClasses.PartialOneWayFlowElement.
Information
This model describes the one-directional pressure driven air flow through an opening based on user-provided tabular data describing the relation between mass flow rate and pressure difference over the component.
ṁ = f(Δp),
where ṁ is the volume flow rate and Δp is the pressure difference.
Based on the table input, a cubic hermite spline is constructed between all points except for the two last pairs of points. These point are connected linearly.
The constructed curve is the direct relation between ṁ and Δp.
A similar model is also used in the CONTAM software (Dols and Walton, 2015).
References
- W. S. Dols and B. J. Polidoro,2015. CONTAM User Guide and Program Documentation Version 3.2, National Institute of Standards and Technology, NIST TN 1887, Sep. 2015. doi: 10.6028/NIST.TN.1887.
Parameters
| Type | Name | Default | Description |
|---|---|---|---|
| Test data | |||
| Modelica.Units.SI.PressureDifference[:] | dpMea_nominal | Pressure difference of test points | |
| Modelica.Units.SI.MassFlowRate[:] | mMea_flow_nominal | Mass flow rate of test points | |
Revisions
-
February 2, 2022, by Michael Wetter:
Revised implementation.
This is for IBPSA, #1436. - Apr 6, 2021, 2020, by Klaas De Jonge:
First implementation.