modelFlowMachine_m

Identical m_flow controlled pumps

Extends from Buildings.Applications.DataCenters.ChillerCooled.Equipment.BaseClasses.PartialPumpParallel.

Information

This model implements a parallel of identical pumps with m_flow being controlled. The number can be specified by setting a value of num. The shutoff valves are used to avoid circulating flow among pumps.

Parameters

TypeNameDefaultDescription
Advanced
Modelica.Units.SI.PressuredpMax2*max(pum.per.pressure.dp) + 6E11Maximum pressure allowed to operate the model, if exceeded, the simulation stops with an error

Components

TypeNameDefaultDescription
Modelica.Blocks.Math.Gain[num]gaiM_flowGain for mass flow rate

Revisions

  • November 16, 2022, by Michael Wetter:
    Improved sequence to avoid switching pump on when the valve is commanded off.
  • July 27, 2017, by Yangyang Fu:
    First implementation.