modelDampers
Validate model for controlling damper position of dual-duct unit with cold-duct minimum control
Information
This example validates BBuildings.Controls.OBC.ASHRAE.G36.TerminalUnits.DualDuctColdDuctMin.Subsequences.Dampers for damper control of dual-duct unit.
Components
| Type | Name | Default | Description |
|---|---|---|---|
| Buildings.Controls.OBC.ASHRAE.G36.TerminalUnits.DualDuctColdDuctMin.Subsequences.Dampers | dam1 | Output signal for controlling damper position | |
| Buildings.Controls.OBC.CDL.Reals.Sources.Ramp | uCoo | Cooling control signal | |
| Buildings.Controls.OBC.CDL.Reals.Sources.Constant | TZon | Zone temperature | |
| Buildings.Controls.OBC.CDL.Reals.Sources.Constant | TCooSup | AHU supply air temperature | |
| Buildings.Controls.OBC.CDL.Reals.Sources.Constant | VActMin_flow | Active minimum airflow setpoint | |
| Buildings.Controls.OBC.CDL.Reals.Sources.Constant | VActCooMax_flow | Active cooling maximum airflow setpoint | |
| Buildings.Controls.OBC.CDL.Reals.Sources.Sin | VColDuc | Cold-duct airflow rate | |
| Buildings.Controls.OBC.CDL.Logical.Sources.Pulse | cooAhu | Cold air handling unit status | |
| Buildings.Controls.OBC.CDL.Reals.Sources.Constant | THeaSup | AHU supply air temperature | |
| Buildings.Controls.OBC.CDL.Reals.Sources.Ramp | uHea | Heating control signal | |
| Buildings.Controls.OBC.CDL.Reals.Sources.Constant | VActHeaMax_flow | Active heating maximum airflow setpoint | |
| Buildings.Controls.OBC.CDL.Logical.Sources.Pulse | heaAhu | Hot air handling unit status | |
| Buildings.Controls.OBC.CDL.Reals.Sources.Sin | VHotDuc | Hot-duct airflow rate |
Revisions
-
February 10, 2022, by Jianjun Hu:
First implementation.