modelPartialDirect
Extends from Buildings.DHC.ETS.BaseClasses.PartialETS.
Information
Direct cooling energy transfer station (ETS) model with in-building pumping and deltaT control. The design is based on a typical district cooling ETS described in ASHRAE's District Cooling Guide. As shown in the figure below, the district and building piping are hydronically coupled. The control valve ensures that the return temperature to the district cooling network is at or above the minimum specified value. This configuration naturally results in a fluctuating building supply tempearture.
Reference
American Society of Heating, Refrigeration and Air-Conditioning Engineers. (2019). Chapter 5: End User Interface. In District Cooling Guide, Second Edition and Owner's Guide for Buildings Served by District Cooling.
Parameters
| Type | Name | Default | Description |
|---|---|---|---|
| Nominal condition | |||
| Modelica.Units.SI.MassFlowRate | mBui_flow_nominal | Nominal mass flow rate of building side | |
| Modelica.Units.SI.PressureDifference | dpConVal_nominal | 50 | Nominal pressure drop in the control valve |
| Modelica.Units.SI.PressureDifference | dpCheVal_nominal | 6000 | Nominal pressure drop in the check valve |
| PID controller | |||
| Modelica.Blocks.Types.SimpleController | controllerType | Modelica.Blocks.Types.SimpleController.PI | Type of controller |
| Real | k | 0.1 | Gain of controller |
| Modelica.Units.SI.Time | Ti | 60 | Time constant of integrator block |
| Modelica.Units.SI.Time | Td | 0.1 | Time constant of derivative block |
| Real | yMax | 1 | Upper limit of output |
| Real | yMin | 0 | Lower limit of output |
| Advanced | |||
| Modelica.Fluid.Types.Dynamics | energyDynamics | Modelica.Fluid.Types.Dynamics.FixedInitial | Type of energy balance: dynamic (3 initialization options) or steady state |
| Real | bandwidth | 0.2 | Bandwidth around reference signal for on/off controller |
Components
| Type | Name | Default | Description |
|---|---|---|---|
| Modelica.Blocks.Interfaces.RealInput | TDisRetSet | Setpoint for the district return temperature (min for cooling, max for heating) | |
| Modelica.Blocks.Interfaces.RealOutput | Q_flow | Measured heating demand at the ETS | |
| Modelica.Blocks.Interfaces.RealOutput | Q | Measured energy consumption at the ETS | |
| Buildings.Fluid.Sensors.TemperatureTwoPort | senTDisSup | District supply temperature sensor | |
| Buildings.Fluid.Sensors.MassFlowRate | senMasFlo | District supply mass flow rate sensor | |
| Buildings.Fluid.FixedResistances.Junction | jun | Bypass junction | |
| Buildings.Fluid.Sensors.TemperatureTwoPort | senTDisRet | District return temperature sensor | |
| Buildings.Fluid.FixedResistances.Junction | spl | Bypass junction, splitter | |
| Buildings.Fluid.Actuators.Valves.TwoWayEqualPercentage | conVal | Control valve | |
| Buildings.Fluid.Sensors.TemperatureTwoPort | senTBuiRet | Building return temperature sensor | |
| Fluid.FixedResistances.CheckValve | cheVal | Check valve (backflow preventer) | |
| Modelica.Blocks.Math.Add | dTDis | Temperature difference on the district side | |
| Modelica.Blocks.Math.Product | pro | Product | |
| Modelica.Blocks.Math.Gain | cp | Specific heat multiplier to calculate heat flow rate | |
| Modelica.Blocks.Continuous.Integrator | int | Integration | |
| Controls.OBC.CDL.Reals.PID | con | District return temperature controller | |
| Buildings.Fluid.Sensors.TemperatureTwoPort | senTBuiSup | Building supply temperature sensor |
Revisions
-
March 11, 2024, by Michael Wetter:
Corrected wrongdisplayUnitstring. -
April 7, 2023, by David Blum:
Changed to partial base class for direct so can extend to heating and cooling ETS. -
January 11, 2023, by Michael Wetter:
Changed controls to use CDL. Changed PID to PI as default for controller. -
January 2, 2023, by Kathryn Hinkelman:
Set pressure drops at junctions to 0 and removed parameterdp_nominal -
December 28, 2022, by Kathryn Hinkelman:
Simplified the control implementation for the district return stream. Improved default control parameters. -
December 23, 2022, by Kathryn Hinkelman:
Removed extraneousm*_flow_nominalparameters becausemBui_flow_nominalcan be used across all components. This is for #2912. -
November 11, 2022, by Michael Wetter:
Changed check valve to use version ofBuildingslibrary, and hence no outersystemis needed. - March 20, 2022, by Chengnan Shi:
Update with base class partial model and standard PI control. - Novermber 13, 2019, by Kathryn Hinkelman:
First implementation.