modelHeatPumpHeatExchanger
Extends from Buildings.DHC.ETS.Combined.BaseClasses.PartialHeatPumpHeatExchanger.
Information
This model uses the base energy transfer station defined in Buildings.DHC.ETS.Combined.BaseClasses.PartialHeatPumpHeatExchanger.
Domestic Hot Water
Domestic hot water is produced using a dedicated water-to-water heat pump on-demand with no storage.
Heating is enabled based on the input signal uSHW
which is held for 15 minutes, meaning that,
when enabled, the mode remains active for at least 15 minutes and,
when disabled, the mode cannot be enabled again for at least 15 minutes.
The enable signal should be computed externally based
on a schedule (to lock out the system during off-hours), ideally in conjunction
with the number of requests or any other signal representative of the load.
When enabled,
- The heat pump and the evaporator and condenser hydronics are controlled based on the principles described in Buildings.DHC.ETS.Combined.Subsystems.HeatPump.
-
The condensor water mass flow rate is computed based on the domestic hot water
heating load (input
QReqHotWat_flow) where the temperature of water is boosted from the domestic cold water temperature (inputTColWat) to the desired domestic hot water distribution temperature (parameterTHotWatSup_nominal), according to the following equation:QReqHotWat_flow= ṁ cp (THotWatSup_nominal-TColWat)
Components
| Type | Name | Default | Description |
|---|---|---|---|
| Buildings.DHC.ETS.Combined.Subsystems.HeatPump | proHotWat | Subsystem for hot water production | |
| Buildings.Fluid.Sources.Boundary_pT | souColWat | Source for cold water | |
| Buildings.Fluid.Sources.Boundary_pT | sinSHW | Sink for service hot water | |
| Buildings.Controls.OBC.CDL.Reals.Divide | div1 | Compute mass flow rate from load | |
| Buildings.Controls.OBC.CDL.Reals.MultiplyByParameter | gai | Times Cp | |
| Buildings.Controls.OBC.CDL.Reals.Subtract | delT | Compute DeltaT needed on condenser side |
Revisions
-
March 27, 2024, by David Blum:
Update icon.
This is for issue #3606. -
September 13, 2023, by David Blum:
Extended from partial base class. This is for issue 3063. -
May 17, 2023, by David Blum:
Assigned dp_nominal topum1HexChi.
Corrected calculation of heat pump evaporator mass flow control.
This is for issue 3379. -
February 23, 2021, by Antoine Gautier:
Refactored with subsystem models and partial ETS base class.
This is for issue 1769. -
December 12, 2017, by Michael Wetter:
Removed call toModelica.Utilities.Files.loadResource.
This is for issue 1097.