modelBuildingTimeSeriesWithETS
Model of a building with loads provided as time series, connected to an ETS for heating
Extends from BaseClasses.PartialBuildingWithETS.
Information
This model is composed of a direct controlled energy transfer station model for heating Buildings.DHC.ETS.Heating.Direct connected to a simplified building model Buildings.DHC.Loads.BaseClasses.BuildingTimeSeries where the space heating loads are provided as time series.
Parameters
| Type | Name | Default | Description |
|---|---|---|---|
| Modelica.Units.SI.HeatFlowRate | QHea_flow_nominal | bui.facMul*bui.QHea_flow_nominal | Space heating design load (>=0) |
| String | filNam | Library path of the file with thermal loads as time series | |
| Nominal condition | |||
| Modelica.Units.SI.TemperatureDifference | dT_nominal | 10 | Water temperature drop/increase accross load and source-side HX (always positive) |
| Modelica.Units.SI.Temperature | THeaWatRet_nominal | THeaWatSup_nominal - dT_nominal | Heating water return temperature |
| Nominal conditions | |||
| Modelica.Units.SI.Temperature | THeaWatSup_nominal | 50 + 273.15 | Heating water supply temperature |
| Dynamics › Conservation equations | |||
| Modelica.Fluid.Types.Dynamics | energyDynamics | Modelica.Fluid.Types.Dynamics.SteadyState | Type of energy balance |
| Dynamics › Pump | |||
| Boolean | use_riseTime | false | Set to true to continuously change motor speed |
Revisions
-
January 12, 2023, by Michael Wetter:
Removed unused parameterriseTime. -
January 2, 2023, by Kathryn Hinkelman:
Propagated energy dynamics and a filter for the (variable) secondary pumps. -
December 23, 2022, by Kathryn Hinkelman:
Revised ETS from direct uncontrolled to direct controlled. This is for #2912. -
December 21, 2022 by Kathryn Hinkelman:
Removed in-building pumping because of coupling with the direct/uncontrolled ETS.
This is for #2912.
- March 20, 2022 by Chengnan Shi:
First implementation.