modelPartialMultiplePumps

Base class for modeling multiple identical pumps in parallel

Extends from Buildings.Fluid.Interfaces.LumpedVolumeDeclarations, Buildings.Fluid.Interfaces.PartialTwoPortInterface.

Information

This base class represents multiple identical pumps that are piped in parallel. An optional check valve in series with each pump is included. This class is used to construct the various multiple-pump models within Buildings.DHC.Plants.Combined.Subsystems.

Details

In a parallel arrangement, all operating units have the same operating point. This allows modeling the multiple pumps with a single instance of any class derived from Buildings.Fluid.Movers.BaseClasses.PartialFlowMachine. Hydronics are resolved with mass flow rate multiplier components.

Parameters

TypeNameDefaultDescription
IntegernPumNumber of pumps
Booleanhave_vartrueSet to true for variable speed pumps, false for constant speed
Booleanhave_valvetrueSet to true for inline check valve
Fluid.Movers.Data.Genericper
Nominal condition
Modelica.Units.SI.MassFlowRatemPum_flow_nominalDesign mass flow rate (each pump)
Modelica.Units.SI.PressureDifferencedpPum_nominalDesign head (each pump)
Modelica.Units.SI.PressureDifferencedpValve_nominal10000Pressure drop of check valve fully open
Dynamics › Nominal condition
Modelica.Units.SI.Timetau1Time constant of fluid volume for nominal flow, used if energy or mass balance is dynamic
Dynamics › Motor speed
Booleanuse_riseTimetrueSet to true to continuously change motor speed
Modelica.Units.SI.TimeriseTime30Time needed to change motor speed between zero and full speed
Modelica.Blocks.Types.InitinitModelica.Blocks.Types.Init.InitialOutputType of initialization (no init/steady state/initial state/initial output)

Components

TypeNameDefaultDescription
Buildings.Controls.OBC.CDL.Interfaces.BooleanInput[nPum]y1Start signal (VFD Run or motor starter contact)
Buildings.Controls.OBC.CDL.Interfaces.RealOutputPTotal power (all pumps)
Buildings.Controls.OBC.CDL.Interfaces.BooleanOutput[nPum]y1_actualPump status
Fluid.BaseClasses.MassFlowRateMultipliermulOutFlow rate multiplier
Fluid.BaseClasses.MassFlowRateMultipliermulInlFlow rate multiplier
Fluid.Movers.SpeedControlled_ypum
Buildings.Templates.Components.Controls.MultipleCommandscomConvert command signal
Buildings.Controls.OBC.CDL.Conversions.BooleanToRealbooToReaConvert to real
Buildings.Controls.OBC.CDL.Reals.MultiplymulCompute total power
Buildings.Controls.OBC.CDL.Reals.MultiplyinpCompute pump input signal
Buildings.Controls.OBC.CDL.Reals.Sources.ConstantcstConstant setpoint
Buildings.Controls.OBC.CDL.Reals.GreaterThresholdisOpeEvaluate if pump is operating
Fluid.FixedResistances.CheckValvecheValCheck valve (optional)
Buildings.DHC.Plants.Combined.Subsystems.BaseClasses.PassThroughFluidpasDirect fluid pass-through (case without check valve)
Buildings.Controls.OBC.CDL.Routing.BooleanScalarReplicatorrepReplicate
Buildings.Controls.OBC.CDL.Logical.Pre[nPum]preY1Left limit of signal avoiding direct feedback of status to controller

Revisions

  • February 24, 2023, by Antoine Gautier:
    First implementation.