modelPartialCoolingTowersSubsystem
Partial class for test models of subsystems
Information
Partial model to test cooling tower models that are connected to a weather data reader
and a simple fluid loop to which a constant amount of heat is added.
The pump in the cooling tower loop is switched on and off depending
on the temperature of the control volume to which the heat is added.
Parameters
| Type | Name | Default | Description |
| Nominal condition |
| Modelica.Units.SI.MassFlowRate | m_flow_nominal | 0.5 | Design water flow rate |
Components
| Type | Name | Default | Description |
| Buildings.Fluid.Interfaces.PartialTwoPortInterface | tow | | |
| Buildings.Fluid.Movers.FlowControlled_m_flow | pum | | Pump for condenser water loop |
| Buildings.BoundaryConditions.WeatherData.ReaderTMY3 | weaDat | | |
| Buildings.BoundaryConditions.WeatherData.Bus | weaBus | | Weather data bus |
| Buildings.Controls.OBC.CDL.Reals.Switch | swi | | Control switch for chilled water pump |
| Buildings.Controls.OBC.CDL.Reals.Sources.Constant | TSwi | | Switch temperature for switching tower pump on |
| Buildings.Controls.OBC.CDL.Reals.Sources.Constant | zer | | Zero flow rate |
| Buildings.Controls.OBC.CDL.Reals.Sources.Constant | m_flow | | Water flow rate |
| Buildings.Fluid.MixingVolumes.MixingVolume | vol | | |
| Buildings.Fluid.Sources.Boundary_pT | exp | | Expansion vessel |
| Modelica.Thermal.HeatTransfer.Sources.FixedHeatFlow | fixHeaFlo | | Fixed heat flow rate |
| Modelica.Thermal.HeatTransfer.Sensors.TemperatureSensor | TVol | | Water temperature |
| Buildings.Fluid.Sensors.TemperatureTwoPort | TEnt | | Water entering temperature |
| Buildings.Controls.OBC.CDL.Reals.Hysteresis | hys | | Pump on-off control |
| Buildings.Controls.OBC.CDL.Reals.Subtract | sub | | Inputs different |
Contents
| Name | Description |
| Medium_W | Medium model for water |