modelChillerSetPointControl
Test model for chiller setpoint control using TrimAndResponse and LinearPieceWiseTwo
Extends from Modelica.Icons.Example.
Parameters
| Type | Name | Default | Description |
| Modelica.Units.SI.MassFlowRate | mAir_flow_nominal | 61.6*2 | Nominal mass flow rate at fan |
| Real | COPc_nominal | 3 | Chiller COP |
| Modelica.Units.SI.MassFlowRate | mCHW_flow_nominal | 15.2 | Nominal mass flow rate at chilled water |
| Modelica.Units.SI.MassFlowRate | mCW_flow_nominal | mCHW_flow_nominal/COPc_nominal*(COPc_nominal + 1) | Nominal mass flow rate at condenser water |
| Real | QRoo | 100 | |
Components
| Type | Name | Default | Description |
| Buildings.Examples.ChillerPlant.BaseClasses.Controls.TrimAndRespond | triAndRes | | |
| Buildings.Examples.ChillerPlant.BaseClasses.Controls.LinearPiecewiseTwo | linPieTwo | | |
| Buildings.Fluid.Chillers.ElectricEIR | chi | | Chiller |
| Buildings.Fluid.HeatExchangers.ConstantEffectiveness | coi | | Cooling coil |
| Buildings.Fluid.Sources.Boundary_pT | sin1 | | |
| Buildings.Fluid.Sources.MassFlowSource_T | sou1 | | |
| Modelica.Blocks.Sources.Constant | const | | |
| Buildings.Controls.Continuous.LimPID | limPID | | PI controller |
| Buildings.Fluid.Sensors.TemperatureTwoPort | TRet | | |
| Buildings.Fluid.Movers.FlowControlled_m_flow | pum | | Chilled water pump |
| Buildings.Fluid.Storage.ExpansionVessel | expVesChi | | |
| Modelica.Blocks.Sources.BooleanConstant | booleanConstant1 | | |
| Modelica.Blocks.Math.Gain | gain | | |
| Buildings.Fluid.Sources.MassFlowSource_T | sou2 | | |
| Buildings.Fluid.Sources.Boundary_pT | sin2 | | |
| Modelica.Blocks.Sources.Sine | sine | | |
| Modelica.Blocks.Continuous.FirstOrder | firstOrder1 | | |
| Buildings.Fluid.Sensors.TemperatureTwoPort | TSup | | |
Contents
| Name | Description |
| Medium1 | |
| Medium2 | |
| MediumAir | Medium model |
Revisions
-
April 9, 2024, by Hongxiang Fu:
Specified nominalValuesDefineDefaultPressureCurve=true
in the mover component to suppress a warning.
This is for
#3819.
-
August 16, 2019, by Michael Wetter:
Changed initialization of PI controller for Dymola 2020.
-
December 22, 2014 by Michael Wetter:
Removed Modelica.Fluid.System
to address issue
#311.
-
March 25, 2014, by Michael Wetter:
Updated model with new expansion vessel.
-
October 17, 2012, by Wangda Zuo:
Revised for the new trim and respond control.
-
July 21, 2011, by Wangda Zuo:
Added mos file and merged to library.
-
January 18, 2011, by Wangda Zuo:
First implementation.