modelMassTransfer
Component that sets the trace substance at the filter outlet
Extends from Buildings.Fluid.Interfaces.PartialTwoPort.
Information
This model sets the trace substance
of the medium that leaves port_b by
port_b.C_outflow = inStream(port_a.C_outflow) - eps * C_inflow;
where eps is an input mass transfer efficiency and
C_inflow is an input trace substance rate.
This model has no pressure drop.
Parameters
| Type | Name | Default | Description |
|---|---|---|---|
| String[:] | namCon | Name of contaminant substance |
Components
| Type | Name | Default | Description |
|---|---|---|---|
| Buildings.Controls.OBC.CDL.Interfaces.RealInput[nConSub] | eps | Filtration efficiency of each contaminant | |
| Buildings.Controls.OBC.CDL.Interfaces.RealOutput[nConSub] | mCon_flow | Contaminant mass flow rate |
Revisions
-
December 22, 2023, by Sen Huang:
First implementation.