modelTableData2D
Extends from Buildings.Fluid.Chillers.ModularReversible.RefrigerantCycle.BaseClasses.PartialChillerCycle, Buildings.Fluid.HeatPumps.ModularReversible.RefrigerantCycle.BaseClasses.PartialTableData2D.
Information
This model uses two-dimensional table data typically given
by manufacturers as required by e.g. European Norm 14511
or ASHRAE 205 to calculate
QEva_flow and PEle.
For different condenser outlet and evaporator inlet temperatures, the tables must provide two of the three following values: electrical power consumption, evaporator heat flow rate, and COP.
Note that losses are often implicitly included in measured data. In this case, the frosting modules should be disabled.
Scaling factor
For the scaling factor, the table data for evaporator heat flow rate (QEvaTabDat_flow)
is evaluated at nominal conditions. Hence, the scaling factor is
scaFac = QEva_flow_nominal/QEvaTabDat_flow(TEva_nominal, TCon_nominal).
Using scaFac, the table data is scaled linearly.
This implies a constant COP over different design sizes:
QEva_flow = scaFac * tabQEva_flow.y
PEle = scaFac * tabPel.y
Known Limitations
- Manufacturers are not required to provide the compressor speed at which the data are measured. Thus, nominal values may be obtained at different compressor speeds and, thus, efficiencies. To accurately model the available thermal output, please check that you use tables of the maximal thermal output, which is often provided in the data sheets from the manufacturers. This limitation only holds for inverter driven chillers.
-
We assume that the efficiency is contant over the whole
compressor speed range. Typically, efficiencies will drop at minimal
and maximal compressor speeds.
To model an inverter controlled chiller, the relative
compressor speed
yMeais used to scale the ouput of the tables linearly. For models including the compressor speed, check the SDF-Library dependent refrigerant cycle models in the AixLib Library.
References
EN 14511-2018: Air conditioners, liquid chilling packages and heat pumps for space heating and cooling and process chillers, with electrically driven compressors https://www.beuth.de/de/norm/din-en-14511-1/298537524
Parameters
| Type | Name | Default | Description |
|---|---|---|---|
| Buildings.Fluid.Chillers.ModularReversible.Data.TableData2D.Generic | datTab | Data Table of Chiller | |
| Nominal condition | |||
| Modelica.Units.SI.HeatFlowRate | QCooNoSca_flow_nominal | Modelica.Blocks.Tables.Internal.getTable2DValueNoDer2(tabIdeQUse_flow, TEva_nominal, TCon_nominal) | Unscaled nominal cooling capacity |
Revisions
-
October 2, 2022 by Fabian Wuellhorst:
Adjusted based on the discussion in this issue #1576) -
May 22, 2019, by Julian Matthes:
First implementation (see issue AixLib #715)