modelTableData2DLoadDep_AirCooled

Test model for chiller electric reformulated EIR

Extends from Modelica.Icons.Example, Buildings.Fluid.Chillers.Examples.BaseClasses.PartialElectric_AirCooled.

Information

This model validates Buildings.Fluid.Chillers.ModularReversible.TableData2DLoadDep against the polynomial chiller model Buildings.Fluid.Chillers.ElectricEIR for air-cooled chiller applications.

Results analysis

There is good agreement with the reference results, except during the time interval where the PLR value exceeds 1. In this interval the polynomial model computes a significantly higher cooling heat flow rate (in negative value) and a slightly higher power. This discrepancy occurs because the polynomial model calculates the heat flow rate at PLR ≤ 1 while calculating power at PLR ≤ per.PLRMax. Consequently, when PLR increases between 1 and per.PLRMax, input power increases according to the polynomial EIRFunPLR, but the heat flow rate only varies due to the effect of the increasing leaving temperature as the setpoint is no longer met. This appears as a deficiency in the polynomial model that is resolved in the data table model.

Parameters

TypeNameDefaultDescription
ModularReversible.Data.TableData2DLoadDep.GenericdatCooChiller performance data
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_York_YCAL0033EE_101kW_3_1COP_AirCooledperChiller performance data

Components

TypeNameDefaultDescription
Buildings.Fluid.Chillers.ModularReversible.TableData2DLoadDepchiChiller
Modelica.Blocks.Sources.CombiTimeTablerefReference results

Revisions

  • March 21, 2025, by Antoine Gautier:
    First implementation.