modelWetCoil

Calculates wet coil condition

Extends from Buildings.Fluid.DXSystems.Cooling.BaseClasses.PartialCoilCondition.

Information

This block calculates the rate of cooling and the coil surface condition under the assumption that the coil is wet.

The dry coil conditions are computed in Buildings.Fluid.DXSystems.BaseClasses.DryCoil. See Buildings.Fluid.DXSystems.Cooling.UsersGuide for an explanation of the model.

Components

TypeNameDefaultDescription
Modelica.Blocks.Interfaces.RealOutputTADPDry bulb temperature of air at ADP
Modelica.Blocks.Interfaces.RealOutputSHRSensible Heat Ratio: Ratio of sensible heat load to total heat load
Modelica.Blocks.Interfaces.RealOutputmWat_flowMass flow rate of water condensed at cooling coil
Buildings.Utilities.Psychrometrics.TWetBul_TDryBulXiwetBulCalculates wet-bulb temperature
Buildings.Fluid.DXSystems.Cooling.BaseClasses.ApparatusDewPointappDewPtCalculates air properties at apparatus dew point (ADP) at existing air-flow conditions
Buildings.Fluid.DXSystems.Cooling.BaseClasses.SensibleHeatRatioshrCalculates sensible heat ratio
Buildings.Fluid.DXSystems.Cooling.BaseClasses.CondensationconRatCalculates rate of condensation
Modelica.Blocks.Interfaces.RealOutputXADPHumidity mass fraction of air at apparatus dew point
Modelica.Blocks.Interfaces.RealInputXEvaInInlet air mass fraction
Modelica.Blocks.Interfaces.RealInputpPressure at inlet of coil
Modelica.Blocks.Interfaces.RealInputhEvaInSpecific enthalpy of air entering the coil

Contents

NameDescription
MediumMedium model

Revisions

  • April 5, 2023, by Xing Lu:
    Connect statements with references to cooCap changed to coiCap.
  • April 12, 2012 by Kaustubh Phalak:
    First implementation.