modelPipeManifoldFixedResistance

Pipe manifold for a heat exchanger connection

Extends from PartialPipeManifold.

Information

Pipe manifold with a fixed flow resistance.

This model is composed of a pressure drop calculation, and a flow distributor. The flow distributor distributes the mass flow rate equally to each instance of port_b, without having to compute a pressure drop in each flow leg.

Note: It is important that there is an equal pressure drop in each flow leg between this model, and the model that collects the flows. Otherwise, no solution may exist, and therefore the simulation may stop with an error.

Parameters

TypeNameDefaultDescription
Booleanuse_dhfalseSet to true to specify hydraulic diameter
Modelica.Units.SI.Lengthdh0.025Hydraulic diameter for each pipe
RealReC4000Reynolds number where transition to turbulence starts
RealdeltaM0.3Fraction of nominal mass flow rate where transition to turbulent occurs
Nominal Condition
Modelica.Units.SI.MassFlowRatem_flow_nominalMass flow rate at port_a
Modelica.Units.SI.PressureDifferencedp_nominalPressure drop
Advanced
Booleanlinearizedfalse= true, use linear relation between m_flow and dp for any flow rate
Booleanfrom_dpfalse= true, use m_flow = f(dp) else dp = f(m_flow)

Components

TypeNameDefaultDescription
Buildings.Fluid.FixedResistances.PressureDropfixResFixed resistance for each duct

Revisions

  • January 22, 2016, by Michael Wetter:
    Corrected type declaration of pressure difference. This is for #404.
  • June 29, 2014, by Michael Wetter:
    Added model that distributes the mass flow rate equally to each instance of port_b.
  • September 10, 2008, by Michael Wetter:
    Added additional parameters.
  • August 22, 2008, by Michael Wetter:
    Added start value for resistance mass flow rate.
  • April 14, 2008, by Michael Wetter:
    First implementation.