recordGeneric
Performance data record for a wet cooling cooler using the York calculation method
Extends from Buildings.Fluid.HeatExchangers.CoolingTowers.Data.BaseClasses.BaseCoolingTower.
Information
Performance data record for a wet cooling cooler using the York calculation methods.
The default settings are for a cooler with a design approach temperature (cooling out - air wet bulb in) of 3.89 K and a design range temperature (cooling in - cooling out) of 5.56 K. This corresponds to a nominal water inlet temperature of 35 °C and a nominal water outlet temperature of 29.44 °C.
Parameters
| Type | Name | Default | Description |
|---|---|---|---|
| Nominal thermal performance | |||
| Modelica.Units.SI.Temperature | TAirInWB_nominal | 298.7 | Nominal outdoor (air inlet) wetbulb temperature |
Revisions
-
April 23, 2026, by Michael Wetter:
First implementation.