modelTableData2DLoadDep

Data-based model dependent on condenser and evaporator entering or leaving temperature and PLR

Extends from Buildings.Fluid.HeatPumps.ModularReversible.RefrigerantCycle.BaseClasses.PartialHeatPumpCycle.

Information

This model serves as a wrapper class to integrate the block Buildings.Fluid.HeatPumps.ModularReversible.RefrigerantCycle.BaseClasses.TableData2DLoadDep into heat pump models. For a complete description of all modeling assumptions, please refer to the documentation of this block.

Parameters

TypeNameDefaultDescription
Booleanuse_revTrue if the refrigerant machine is reversible
RealscaFacQHea_flow_nominal/calQUseP.Q_flow_nominalScaling factor
Booleanuse_TEvaOutForTabdat.use_TEvaOutForTab=true to use evaporator outlet temperature, false for inlet
Booleanuse_TConOutForTabdat.use_TConOutForTab=true to use condenser outlet temperature, false for inlet
Booleanuse_TLoaLvgForCtltrueSet to true for leaving temperature control, false for entering temperature control
Buildings.Fluid.HeatPumps.ModularReversible.Data.TableData2DLoadDep.GenericHeatPumpdatTable with performance data
Modelica.Units.SI.PowerP_min0Minimum power when system is enabled with compressor cycled off

Components

TypeNameDefaultDescription
BaseClasses.TableData2DLoadDepcalQUsePCompute heat flow rate and input power
Buildings.Controls.OBC.CDL.Reals.Sources.Constant[2]cpSpecific heat capacity
Buildings.Controls.OBC.CDL.Routing.RealExtractor[6]extBusSigExtract bus signals depending on application
Buildings.Controls.OBC.CDL.Integers.Sources.Constant[2]cstConstants
Buildings.Controls.OBC.CDL.Integers.SwitchintSwiSelection index: 1 to use evaporator as load side, 2 to use condenser
Buildings.Controls.OBC.CDL.Routing.IntegerScalarReplicatorintScaRepReplicate selection index
Buildings.Controls.OBC.CDL.Logical.Sources.Constantuse_inHpConstant Boolean
Buildings.Controls.OBC.CDL.Logical.NotnotCooCooling disabled (if used in chiller)
Buildings.Controls.OBC.CDL.Routing.BooleanScalarReplicatorheaHeating enable (if used in reversible heat pump)
Buildings.Controls.OBC.CDL.Logical.Sources.ConstanttruPlaceholder signal for heating-only system
Buildings.Controls.OBC.CDL.Logical.AndonAndHeaTrue if enabled in heating mode
Buildings.Controls.OBC.CDL.Reals.SwitchTSetActSwitch between CHW and HW temperature setpoint

Revisions

  • March 23, 2026, by Antoine Gautier:
    Refactored with two separate connectors for HW and CHW temperature setpoints.
    This is for #4507.
  • March 21, 2025, by Antoine Gautier:
    First implementation.