modelLimits_LoopDisable
Validation model for the multi zone VAV AHU minimum outdoor air control - damper position limits
Information
This example validates enable/disable conditions for
Buildings.Obsolete.Controls.OBC.ASHRAE.G36_PR1.AHUs.MultiZone.VAV.Economizers.Subsequences.Limits
for the following input signals: uSupFan, uFreProSta, uOpeMod.
Components
| Type | Name | Default | Description |
|---|---|---|---|
| Buildings.Controls.OBC.CDL.Reals.Sources.Constant | VOutMinSet_flow | Outdoor airflow rate setpoint, 15cfm/occupant and 100 occupants | |
| Buildings.Controls.OBC.CDL.Reals.Sources.Constant | VOutMinSet1_flow | Outdoor airflow rate setpoint, 15cfm/occupant and 100 occupants | |
| Buildings.Controls.OBC.CDL.Reals.Sources.Constant | VOutMinSet2_flow | Outdoor airflow rate setpoint, 15cfm/occupant and 100 occupants | |
| Buildings.Controls.OBC.CDL.Logical.Sources.Constant | fanSta | Fan is off | |
| Buildings.Controls.OBC.CDL.Integers.Sources.Constant | opeMod1 | AHU operation mode is NOT Occupied | |
| Buildings.Controls.OBC.CDL.Integers.Sources.Constant | freProSta2 | Freeze protection stage is 2 | |
| Buildings.Controls.OBC.CDL.Reals.Sources.Ramp | VOut_flow | Measured outdoor airflow rate | |
| Buildings.Controls.OBC.CDL.Reals.Sources.Ramp | VOut1_flow | Measured outdoor airflow rate | |
| Buildings.Controls.OBC.CDL.Reals.Sources.Ramp | VOut2_flow | Measured outdoor airflow rate | |
| Buildings.Obsolete.Controls.OBC.ASHRAE.G36_PR1.AHUs.MultiZone.VAV.Economizers.Subsequences.Limits | damLim | Multi zone VAV AHU minimum outdoor air control - damper position limits | |
| Buildings.Obsolete.Controls.OBC.ASHRAE.G36_PR1.AHUs.MultiZone.VAV.Economizers.Subsequences.Limits | damLim1 | Multi zone VAV AHU minimum outdoor air control - damper position limits | |
| Buildings.Obsolete.Controls.OBC.ASHRAE.G36_PR1.AHUs.MultiZone.VAV.Economizers.Subsequences.Limits | damLim2 | Multi zone VAV AHU minimum outdoor air control - damper position limits |
Revisions
-
June 06, 2017, by Milica Grahovac:
First implementation.