blockPartialControllerVAVMultizone

Interface class for multiple-zone VAV controller

Extends from Buildings.Templates.AirHandlersFans.Components.Interfaces.PartialController.

Information

This partial class provides a standard interface for multiple-zone VAV controllers.

Parameters

TypeNameDefaultDescription
Booleanhave_freProtrueSet to true to include freeze protection
Buildings.Controls.OBC.ASHRAE.G36.Types.FreezeStattypFreStaBuildings.Controls.OBC.ASHRAE.G36.Types.FreezeStat.No_freeze_statOption for low limit (freeze) protection
Buildings.Controls.OBC.ASHRAE.G36.Types.EnergyStandardstdEnedatAll.stdEneEnergy standard
Buildings.Controls.OBC.ASHRAE.G36.Types.VentilationStandardstdVendatAll.stdVenVentilation standard
Economizer
Buildings.Controls.OBC.ASHRAE.G36.Types.ControlEconomizertypCtlEcoBuildings.Controls.OBC.ASHRAE.G36.Types.ControlEconomizer.FixedDryBulbEconomizer control type
Booleanuse_TMixtrueSet to true if mixed air temperature measurement is enabled
Buildings.Controls.OBC.ASHRAE.G36.Types.OutdoorAirSectiontypSecOutsecOutRel.typSecOutType of outdoor air section
Buildings.Controls.OBC.ASHRAE.G36.Types.PressureControlbuiPreConif secOutRel.typSecRel == Buildings.Templates.AirHandlersFans.Types.ReliefReturnSection.ReliefDamper then Buildings.Controls.OBC.ASHRAE.G36.Types.PressureControl.ReliefDamper elseif secOutRel.typSecRel == Buildings.Templates.AirHandlersFans.Types.ReliefReturnSection.ReliefFan then Buildings.Controls.OBC.ASHRAE.G36.Types.PressureControl.ReliefFan elseif secOutRel.typSecRel == Buildings.Templates.AirHandlersFans.Types.ReliefReturnSection.ReturnFan then (if typCtlFanRet == Buildings.Templates.AirHandlersFans.Types.ControlFanReturn.AirflowMeasured then Buildings.Controls.OBC.ASHRAE.G36.Types.PressureControl.ReturnFanMeasuredAir elseif typCtlFanRet == Buildings.Templates.AirHandlersFans.Types.ControlFanReturn.BuildingPressure then Buildings.Controls.OBC.ASHRAE.G36.Types.PressureControl.ReturnFanDp else Buildings.Controls.OBC.ASHRAE.G36.Types.PressureControl.ReliefDamper) else Buildings.Controls.OBC.ASHRAE.G36.Types.PressureControl.ReliefDamperType of building pressure control system
Configuration
Buildings.Templates.AirHandlersFans.Types.ControlFanReturntypCtlFanRetBuildings.Templates.AirHandlersFans.Types.ControlFanReturn.AirflowMeasuredReturn fan control type
Booleanhave_CO2SenfalseSet to true if there are zones with CO2 sensor

Components

TypeNameDefaultDescription
Buildings.Templates.AirHandlersFans.Components.Interfaces.PartialOutdoorReliefReturnSectionsecOutRelOutdoor/relief/return air section
Buildings.Templates.Components.Coils.NonecoiCooCooling coil
Buildings.Templates.Components.Coils.NonecoiHeaPreHeating coil (preheat position)
Buildings.Templates.Components.Coils.NonecoiHeaRehHeating coil (reheat position)