modelPartialHeatPumpTableData2DLoadDep
Interface for heat pump using load-dependent 2D table data
Extends from Buildings.Templates.Components.Interfaces.PartialHeatPump.
Information
This is the base class for heat pump models where the capacity
and input power are computed by interpolating manufacturer data
along the condenser entering or leaving temperature, the
evaporator entering or leaving temperature and the part load ratio.
Toggling the Boolean parameter is_rev enables
representing either a non-reversible (heating-only) heat pump or a
reversible heat pump.
This model is a wrapper for Buildings.Fluid.HeatPumps.ModularReversible.TableData2DLoadDep, which the user may refer to for the modeling assumptions.
Control points
The following input and output points are available.
-
Heat pump on/off command signal:
y1, DO signal, with a dimensionality of zero - For reversible heat pumps only (
is_rev=true), heat pump operating mode command signal:y1Hea, DO signal, with a dimensionality of zero
Sety1Hea=truefor heating mode,y1Hea=falsefor cooling mode. -
Heat pump HW supply temperature setpoint:
THeaWatSet, AO signal, with a dimensionality of zero - For reversible heat pumps only (
is_rev=true), Heat pump CHW supply temperature setpoint:TChiWatSet, AO signal, with a dimensionality of zero -
Heat pump status:
y1_actual, DI signal, with a dimensionality of zero
Components
| Type | Name | Default | Description |
|---|---|---|---|
| Controls.StatusEmulator | y1_actual | Compute heat pump status | |
| Fluid.Sensors.MassFlowRate | mChiHeaWat_flow | CHW/HW mass flow rate | |
| Fluid.Sensors.TemperatureTwoPort | TChiHeaWatEnt | CHW/HW entering temperature | |
| Fluid.Sensors.TemperatureTwoPort | TChiHeaWatLvg | CHW/HW leaving temperature | |
| Fluid.Sensors.TemperatureTwoPort | TSouEnt | Source fluid entering temperature | |
| Fluid.Sensors.TemperatureTwoPort | TSouLvg | Source fluid leaving temperature | |
| Buildings.Fluid.HeatPumps.ModularReversible.TableData2DLoadDep | hp | Heat pump |
Revisions
-
March 23, 2026, by Antoine Gautier:
Refactored with two separate connectors for HW and CHW temperature setpoints.
This is for #4507. -
March 21, 2025, by Antoine Gautier:
First implementation.