blockFailsafeCondition
Evaluate failsafe stage up condition
Information
For heating applications with primary-secondary distribution: The failsafe stage up condition evaluates to true if either of the following is true.
-
Secondary HW supply temperature < primary HW supply temperature -
dTfor a period ofdtSecand secondary HW supply temperature < setpoint –dTfordtSec. -
Primary HW supply temperature < setpoint -
dTfordtPri.
For heating applications with primary-only distribution: The failsafe stage up condition evaluates to true if the following is true.
-
Primary HW supply temperature < setpoint -
dTfordtPri.
For cooling applications with primary-secondary distribution: The failsafe stage up condition evaluates to true if either of the following is true.
-
Secondary CHW supply temperature > primary CHW supply temperature +
dTfor a period ofdtSecand secondary CHW supply temperature < setpoint +dTfordtSec. -
Primary CHW supply temperature > setpoint +
dTfordtPri.
For cooling applications with primary-only distribution: The failsafe stage up condition evaluates to true if the following is true.
-
Primary CHW supply temperature > setpoint +
dTfordtPri.
Parameters
| Type | Name | Default | Description |
|---|---|---|---|
| Buildings.Templates.Plants.Controls.Types.Application | typ | Type of application | |
| Boolean | have_pumSec | Set to true for primary-secondary distribution, false for primary-only | |
| Real | dT | Delta-T triggering stage up command (>0) | |
| Real | dtPri | 900 | Runtime with high primary-setpoint Delta-T before staging up |
| Real | dtSec | 600 | Runtime with high secondary-primary and secondary-setpoint Delta-T before staging up |
Components
| Type | Name | Default | Description |
|---|---|---|---|
| Buildings.Controls.OBC.CDL.Interfaces.RealInput | TSecSup | Secondary supply temperature | |
| Buildings.Controls.OBC.CDL.Interfaces.RealInput | TPriSup | Primary supply temperature | |
| Buildings.Controls.OBC.CDL.Interfaces.RealInput | TSupSet | Supply temperature setpoint | |
| Buildings.Controls.OBC.CDL.Reals.Subtract | dTSecPri | Secondary-primary ∆T | |
| Buildings.Controls.OBC.CDL.Reals.Subtract | dTPriSet | Primary-setpoint ∆T | |
| Buildings.Controls.OBC.CDL.Reals.MultiplyByParameter | polHeaCoo | Polarity depending on heating or cooling application | |
| Buildings.Controls.OBC.CDL.Reals.MultiplyByParameter | polHeaCoo1 | Polarity depending on heating or cooling application | |
| Buildings.Controls.OBC.CDL.Reals.LessThreshold | lesPriSet | True if Delta-T less than threshold | |
| Buildings.Controls.OBC.CDL.Reals.LessThreshold | lesSecPri | True if Delta-T less than threshold | |
| Buildings.Controls.OBC.CDL.Interfaces.BooleanInput | reset | Reset timers to zero at completion of stage change | |
| Utilities.TimerWithReset | timPriSet | Timer | |
| Utilities.TimerWithReset | timSecPri | Timer | |
| Buildings.Controls.OBC.CDL.Logical.Or | any | Any criterion met | |
| Buildings.Controls.OBC.CDL.Interfaces.BooleanOutput | y1 | Failsafe stage up condition met | |
| Utilities.PlaceholderLogical | ph | Placeholder signal | |
| Buildings.Controls.OBC.CDL.Reals.Subtract | dTSecSet | Secondary-setpoint ∆T | |
| Buildings.Controls.OBC.CDL.Reals.MultiplyByParameter | polHeaCoo2 | Polarity depending on heating or cooling application | |
| Buildings.Controls.OBC.CDL.Reals.LessThreshold | lesSecSet | True if Delta-T less than threshold | |
| Utilities.TimerWithReset | timSecSet | Timer | |
| Buildings.Controls.OBC.CDL.Logical.And | allSec | All criteria on secondary temperature met |