modelHeatRecoveryChiller

Heat recovery chiller for sidestream integration

Extends from Buildings.Fluid.Interfaces.PartialFourPortInterface.

Information

Model of a heat recovery chiller with constant speed CHW and HW pumps. The model is intended to represent the sidestream integration of a HRC into a heating and cooling plant. In such a configuration, the condenser is connected to the HW return and the evaporator is connected to the CHW return.

Control points

The following input and output points are available.

Parameters

TypeNameDefaultDescription
Buildings.Templates.Components.Data.PumpSingledatPumChiWatHRC CHW pump parameters
Buildings.Templates.Components.Data.PumpSingledatPumHeaWatHRC HW pump parameters
Buildings.Templates.Components.Data.ChillerdatHrcHRC parameters
Modelica.Units.SI.MassFlowRatemChiWat_flow_nominalhrc.mChiWat_flow_nominalDesign CHW mass flow rate
Modelica.Units.SI.MassFlowRatemCon_flow_nominalhrc.mCon_flow_nominalDesign condenser cooling fluid mass flow rate
Modelica.Units.SI.HeatFlowRateQChiWat_flow_nominalhrc.QChiWat_flow_nominalDesign cooling heat flow rate
Modelica.Units.SI.PressureDifferencedpChiWat_nominalhrc.dpChiWat_nominalDesign CHW pressure drop
Modelica.Units.SI.PressureDifferencedpCon_nominalhrc.dpCon_nominalDesign condenser cooling fluid pressure drop
Modelica.Units.SI.TemperatureTChiWatSup_nominalhrc.TChiWatSup_nominalDesign CHW supply temperature
Modelica.Units.SI.TemperatureTChiWatRet_nominalhrc.TChiWatRet_nominalDesign CHW return temperature
Modelica.Units.SI.HeatFlowRateQCon_flow_nominalhrc.QCon_flow_nominalDesign condenser heat flow rate
Modelica.Units.SI.TemperatureTConEnt_nominalhrc.TConEnt_nominalDesign condenser entering fluid temperature
Modelica.Units.SI.TemperatureTConLvg_nominalhrc.TConLvg_nominalDesign condenser leaving fluid temperature
Dynamics › Nominal condition
Modelica.Units.SI.TimetauHrc30HRC – Time constant at nominal flow, used if energy or mass balance is dynamic
Modelica.Units.SI.TimetauPum1Pump – Time constant of fluid volume for nominal flow, used if energy or mass balance is dynamic
Dynamics › Conservation equations
Modelica.Fluid.Types.DynamicsenergyDynamicsModelica.Fluid.Types.Dynamics.DynamicFreeInitialType of energy balance: dynamic (3 initialization options) or steady state

Components

TypeNameDefaultDescription
Buildings.Templates.Plants.HeatPumps.Interfaces.BusbusPlant control bus
Buildings.Templates.Components.Chillers.CompressionhrcHeat recovery chiller
Buildings.Templates.Components.Pumps.SinglepumChiWatHRC CHW pump
Buildings.Templates.Components.Pumps.SinglepumHeaWatHRC HW pump

Contents

NameDescription
MediumChiWat
MediumHeaWat

Revisions

  • April 18, 2025, by Antoine Gautier:
    Refactored with load-dependent 2D table data heat recovery chiller model.
    This is for #4152.
  • May 31, 2024, by Antoine Gautier:
    First implementation.