recordHeatPumpPlant
Configuration parameters for heat pump plant
Extends from Modelica.Icons.Record.
Information
This record provides the set of configuration parameters for the heat pump plant models within Buildings.Templates.Plants.HeatPumps.
Parameters
| Type | Name | Default | Description |
|---|---|---|---|
| Buildings.Templates.Components.Types.HeatPump | typ | Type of heat pump | |
| Boolean | have_heaWat | Set to true if the plant provides HW | |
| Boolean | have_hotWat | Set to true if the plant provides DHW | |
| Boolean | have_chiWat | Set to true if the plant provides CHW | |
| Boolean | have_hrc | Set to true for plants with a sidestream heat recovery chiller | |
| Integer | nHp | Number of heat pumps | |
| Boolean | is_rev | Set to true for reversible heat pumps, false for heating only | |
| Boolean | have_valHpInlIso | Set to true for isolation valves at HP inlet | |
| Boolean | have_valHpOutIso | Set to true for isolation valves at HP outlet | |
| Buildings.Templates.Plants.HeatPumps.Types.Controller | typCtl | Type of controller | |
| Integer | nAirHan | Number of air handling units served by the plant | |
| Integer | nEquZon | Number of terminal units (zone equipment) served by the plant | |
| Modelica.Units.SI.Density | rhoHeaWat_default | HW default density | |
| Modelica.Units.SI.SpecificHeatCapacity | cpHeaWat_default | HW default specific heat capacity | |
| Modelica.Units.SI.Density | rhoChiWat_default | CHW default density | |
| Modelica.Units.SI.SpecificHeatCapacity | cpChiWat_default | CHW default specific heat capacity | |
| Modelica.Units.SI.Density | rhoSou_default | Source fluid default density | |
| Modelica.Units.SI.SpecificHeatCapacity | cpSou_default | Source fluid default specific heat capacity | |
| Buildings.Templates.Plants.HeatPumps.Types.PumpsPrimary | typPumHeaWatPri | Type of primary HW pumps | |
| Integer | nPumHeaWatPri | Number of primary HW pumps | |
| Integer | nPumHeaWatSec | Number of secondary HW pumps | |
| Boolean | have_valHeaWatMinByp | Set to true if the HW loop has a minimum flow bypass valve | |
| Buildings.Templates.Components.Types.PumpArrangement | typArrPumPri | Type of primary pump arrangement | |
| Boolean | have_pumHeaWatPriVar | Set to true for variable speed primary HW pumps | |
| Buildings.Templates.Components.Types.IntegrationPoint | typTanHeaWat | Specify if there is a HW buffer tank and where it is integrated into the system | |
| Buildings.Templates.Plants.HeatPumps.Types.PumpsSecondary | typPumHeaWatSec | Type of secondary HW pumps | |
| Buildings.Templates.Plants.HeatPumps.Types.Distribution | typDis | Type of CHW/HW distribution system | |
| Boolean | have_senDpHeaWatRemWir | Set to true for remote HW differential pressure sensor(s) hardwired to plant or pump controller | |
| Integer | nSenDpHeaWatRem | Number of remote HW differential pressure sensors used for HW pump speed control | |
| Boolean | have_pumChiWatPriDed | Set to true for plants with separate dedicated primary CHW pumps | |
| Buildings.Templates.Plants.HeatPumps.Types.PumpsPrimary | typPumChiWatPri | Type of primary CHW pumps | |
| Integer | nPumChiWatPri | Number of primary CHW pumps | |
| Integer | nPumChiWatSec | Number of secondary CHW pumps | |
| Boolean | have_valChiWatMinByp | Set to true if the CHW loop has a minimum flow bypass valve | |
| Boolean | have_pumChiWatPriVar | Set to true for variable speed primary CHW pumps | |
| Buildings.Templates.Components.Types.IntegrationPoint | typTanChiWat | Specify if there is a CHW buffer tank and where it is integrated into the system | |
| Buildings.Templates.Plants.HeatPumps.Types.PumpsSecondary | typPumChiWatSec | Type of secondary CHW pumps | |
| Boolean | have_senDpChiWatRemWir | Set to true for remote CHW differential pressure sensor(s) hardwired to plant or pump controller | |
| Integer | nSenDpChiWatRem | Number of remote CHW differential pressure sensors used for CHW pump speed control | |
| Boolean | have_inpSch | Set to true to provide schedule via software input point |