blockBASControlPoints

Emulation of control points from the BAS

Extends from Modelica.Blocks.Icons.Block.

Information

This class generates signals typically provided by the BAS. It is aimed for validation purposes only.

Parameters

TypeNameDefaultDescription
IntegernZon2Number of served zones

Components

TypeNameDefaultDescription
Interfaces.Bus[nZon]busTerTerminal unit control bus
Controls.OBC.CDL.Logical.Sources.Constant[nZon]y1OccSchScheduled occupancy
Controls.OBC.CDL.Integers.Sources.Constant[nZon]yOveFloSetOverride flow setpoint, 1: set to zero; 2: set to cooling maximum; 3: set to minimum; 4: set to heating maximum
Controls.OBC.CDL.Logical.Sources.Constant[nZon]y1OveHeaOffOverride heating coil valve position, true: close valve
Controls.OBC.CDL.Integers.Sources.Constant[nZon]yOveDamPosOverride damper position, 1: set to close; 2: set to open
Controls.OBC.CDL.Reals.Sources.Constant[nZon]TZonHeaOccSetOccupied heating setpoint
Controls.OBC.CDL.Reals.Sources.Constant[nZon]TZonCooOccSetOccupied cooling setpoint
Controls.OBC.CDL.Reals.Sources.Constant[nZon]TZonHeaUnoSetUnoccupied heating setpoint
Controls.OBC.CDL.Reals.Sources.Constant[nZon]TZonCooUnoSetUnoccupied cooling setpoint
Controls.OBC.CDL.Reals.Sources.Constant[nZon]ppmCO2SetZone CO2 concentration setpoint