modelCase600

Case 600FF, but with dual-setpoint for heating and cooling

Extends from Case600FF.

Information

This model is used for the basic test case 600 of the BESTEST validation suite. Case 600 is a light-weight building with room temperature control set to 20°C for heating and 27°C for cooling. The room has no shade and a window that faces south.

Parameters

TypeNameDefaultDescription
Buildings.ThermalZones.Detailed.Validation.BESTEST.Data.CriteriaLimitsheaCriAnnual heating load limits of the test acceptance criteria from ASHRAE/ANSI Standard 140
Buildings.ThermalZones.Detailed.Validation.BESTEST.Data.CriteriaLimitscooCriAnnual cooling load limits of the test acceptance criteria from ASHRAE/ANSI Standard 140

Components

TypeNameDefaultDescription
Buildings.Controls.OBC.CDL.Reals.PIDconHeaController for heating
Buildings.Controls.OBC.CDL.Reals.PIDconCooController for cooling
Buildings.Controls.OBC.CDL.Reals.MultiplyByParametergaiHeaGain for heating
Buildings.Controls.OBC.CDL.Reals.MultiplyByParametergaiCooGain for cooling
Modelica.Blocks.Math.SumsumHeaCooSum of heating and cooling heat flow rate
Modelica.Blocks.Routing.Multiplex2multiplex2
Modelica.Thermal.HeatTransfer.Sources.PrescribedHeatFlowpreHeaPrescribed heat flow for heating and cooling
Modelica.Blocks.Continuous.IntegratorEHeaHeating energy in Joules
Modelica.Blocks.Continuous.IntegratorECooCooling energy in Joules
BaseClasses.DayScheduleTSetHeaHeating setpoint
BaseClasses.DayScheduleTSetCooCooling setpoint
Buildings.Controls.OBC.CDL.Reals.MovingAveragePHeaHourly averaged heating power
Buildings.Controls.OBC.CDL.Reals.MovingAveragePCooHourly averaged cooling power
Modelica.Blocks.Sources.RealExpressionhGloHorGlobal horizontal solar irradiance
Modelica.Blocks.Continuous.IntegratorgloHorAnnual global horizontal solar irradiance
Modelica.Blocks.Continuous.IntegratorgloSouAnnual south global solar irradiance
Modelica.Blocks.Continuous.IntegratortraSolAnnual transmitted solar irradiance
Modelica.Blocks.Sources.RealExpressionTSkyTemBlack body sky temperature
Buildings.Controls.OBC.CDL.Reals.MovingAverageTSkyTemHouHourly averaged sky temperature
Buildings.Controls.OBC.CDL.Reals.MovingAverageTSkyTemAnnAnnual averaged sky temperature

Revisions

  • May 12, 2023, by Jianjun Hu:
    Added test acceptance criteria limits. This is for issue 3396.
  • April 8, 2020, by Michael Wetter:
    Removed initType in PID controller.
  • January 21, 2020, by Michael Wetter:
    Changed calculation of time averaged values to use Buildings.Controls.OBC.CDL.Reals.MovingMean because this does not trigger a time event every hour.
    This is for issue 1714.
  • July 15, 2012, by Michael Wetter:
    Changed computation of power to use hourly averaged power instead of instantaneous power in order to avoid peaks after set point changes. This is required because the Modelica model is solved using a continuous time solver, whereas the BESTEST reference results were obtained using simulators with discrete time steps. Changed base class to be Buildings.ThermalZones.Detailed.Validation.BESTEST.Cases6xx.Case600FF.
  • July 14, 2012, by Michael Wetter:
    Changed units of integrator to use Joules instead of MWh.
  • October 6, 2011, by Michael Wetter:
    First implementation.