modelCase695

Case 600, but with increased exterior wall and roof insulation and single cooling and heating setpoint

Extends from Buildings.ThermalZones.Detailed.Validation.BESTEST.Cases6xx.Case600.

Information

This model is the case 695 of the BESTEST validation suite. Case 695 differs from case 600 in that it has increased exterior wall and roof insulation and it has single heating and cooling setpoint.

  • Heat = on if zone temperature is below 20°C
  • Cool = on if zone temperature is above 20°C

Parameters

TypeNameDefaultDescription
Buildings.ThermalZones.Detailed.Validation.BESTEST.Data.ExteriorWallCase680extWalCase680Exterior wall
Buildings.ThermalZones.Detailed.Validation.BESTEST.Data.RoofCase680roofCase680Roof

Revisions

  • May 12, 2023, by Jianjun Hu:
    Added test acceptance criteria limits. This is for issue 3396.
  • May 18, 2022, by Jianjun Hu:
    First implementation.