modelCase960
Case 900, but with an unconditioned sun-space
Extends from Buildings.ThermalZones.Detailed.Validation.BESTEST.Cases6xx.Case600.
Information
This model is used for the test case 960 of the BESTEST validation suite. Case 960 is a two zones building, whereas the south-facing zone is an unconditioned sun-space.
Parameters
| Type | Name | Default | Description |
|---|---|---|---|
| Buildings.HeatTransfer.Data.OpaqueConstructions.Brick120 | matLayPar | Construction material for partition walls | |
| Buildings.ThermalZones.Detailed.Validation.BESTEST.Data.ExteriorWallCase900 | extWalCase900 | Exterior wall | |
| Buildings.ThermalZones.Detailed.Validation.BESTEST.Data.FloorCase900 | floorCase900 | Floor |
Components
| Type | Name | Default | Description |
|---|---|---|---|
| Buildings.HeatTransfer.Conduction.MultiLayer | parWal | Partition wall between the two rooms | |
| Buildings.ThermalZones.Detailed.MixedAir | sunSpa | Room model for sun-space | |
| Modelica.Blocks.Sources.Constant | qConGai_flow1 | Convective heat gain | |
| Modelica.Blocks.Sources.Constant | qRadGai_flow1 | Radiative heat gain | |
| Modelica.Blocks.Routing.Multiplex3 | multiplex3_2 | ||
| Modelica.Blocks.Sources.Constant | qLatGai_flow1 | Latent heat gain | |
| Buildings.Fluid.Sources.MassFlowSource_T | sinInf2 | Sink model for sunspace infiltration | |
| Modelica.Blocks.Sources.Constant | InfiltrationRate1 | 0.414 ACH adjusted for the altitude (0.5 at sea level) | |
| Modelica.Blocks.Math.Product | product1 | ||
| Buildings.Fluid.Sensors.Density | density1 | Air density inside the building | |
| Buildings.Fluid.FixedResistances.PressureDrop | heaCoo1 | Heater and cooler | |
| Buildings.HeatTransfer.Convection.Exterior | conOpa1 | Convection model for opaque part of the wall | |
| Modelica.Thermal.HeatTransfer.Sensors.TemperatureSensor | TSunSpaAir | Sun space room air temperature | |
| Buildings.Controls.OBC.CDL.Reals.MovingAverage | TSunSpaHou | Hourly averaged room air temperature | |
| Buildings.Controls.OBC.CDL.Reals.MovingAverage | TSunSpaAnn | Annual averaged room air temperature |
Revisions
-
March 26, 2024, by Michael Wetter:
Configured the sensor parameter to suppress the warning about being a one-port connection.
This is for #3731 -
May 12, 2023, by Jianjun Hu:
Added test acceptance criteria limits. This is for issue 3396. -
September 16, 2021, by Michael Wetter:
Removed assignment of parameterlatas this is now obtained from the weather data reader.
This is for IBPSA, #1477. -
October 9, 2013, by Michael Wetter:
Corrected assignment of soil properties to avoid an error when checking the model in pedantic mode. -
May 1, 2013, by Michael Wetter:
Declared the parameter record to be a parameter, as declaring its elements to be parameters does not imply that the whole record has the variability of a parameter. -
July 16, 2012, by Michael Wetter:
First implementation.