modelCase910

Case 900, but the window has an overhang

Extends from Buildings.ThermalZones.ISO13790.Validation.BESTEST.Cases9xx.Case900.

Information

This model is the case 910 of the BESTEST validation suite. Case 910 differs from case 900 in that the south-oriented window has an overhang of 1 meter.

Implementation

The shading reduction factor was set to 0.84. This value was calculated based on Table G.6 of the ISO13790 standard.

Revisions

  • May 2, 2024, by Alessandro Maccarini:
    First implementation.