modelControlsVerification_CoolingCoilValve
Validation model for the cooling coil control subsequence with recorded data trends
Extends from Modelica.Icons.Example.
Information
This model validates the cooling coil signal subsequence implemented in Building 33 on the main LBNL campus. Data used for the validation are measured input and output trends with 5s time steps, starting at 2018-06-07 00:00:00 PDT. The trends were exported from the ALC EIKON webserver.
Components
| Type | Name | Default | Description |
|---|---|---|---|
| Modelica.Blocks.Sources.CombiTimeTable | TOut_F | Measured outdoor air temperature | |
| Modelica.Blocks.Sources.CombiTimeTable | TSupSetpoint_F | Supply air temperature setpoint | |
| Modelica.Blocks.Sources.CombiTimeTable | coolingValveSignal | Output of the cooling valve control subsequence | |
| Modelica.Blocks.Sources.CombiTimeTable | fanFeedback | Fan feedback | |
| Modelica.Blocks.Sources.CombiTimeTable | fanStatus | Fan status | |
| Modelica.Blocks.Sources.CombiTimeTable | TSupply_F | Measured supply air temperature | |
| Buildings.Utilities.Plotters.Examples.BaseClasses.CoolingCoilValve | cooValSta | Cooling valve position control sequence | |
| Buildings.Controls.OBC.CDL.Reals.GreaterThreshold | greThr | Converter to boolean | |
| Buildings.Controls.OBC.CDL.Reals.MultiplyByParameter | percConv | Converter from percentage | |
| Buildings.Controls.OBC.CDL.Reals.MultiplyByParameter | percConv1 | Converter from percentage | |
| Buildings.Controls.OBC.UnitConversions.From_degF | from_degF | Unit Converter | |
| Buildings.Controls.OBC.UnitConversions.From_degF | from_degF1 | Unit Converter | |
| Buildings.Controls.OBC.UnitConversions.From_degF | from_degF2 | Unit Converter | |
| Buildings.Controls.OBC.UnitConversions.To_degC | to_degC | Unit Converter | |
| Buildings.Controls.OBC.UnitConversions.To_degC | to_degC1 | Unit Converter | |
| Buildings.Controls.OBC.UnitConversions.To_degC | to_degC2 | Unit Converter |
Revisions
-
April 10, Milica Grahovac
First implementation.