modelStaticCase
Extends from Modelica.Icons.Example (Icon for runnable examples).
Information
It is a static version of the double inertia test case to easily calculate initial values for the time-domain example.
Parameters
| Type | Name | Default | Description |
| Dynawo.Types.VoltageModule | UNom | 400 | Nominal voltage for the test case |
| Dynawo.Types.PerUnit | R1Pu | 0.02*Dynawo.Electrical.SystemBase.SnRef/(UNom*UNom) | Line resistance in pu (base SnRef/UNom) by kilometer for branch 1 |
| Dynawo.Types.PerUnit | X1Pu | 0.27*Dynawo.Electrical.SystemBase.SnRef/(UNom*UNom) | Line reactance in pu (base SnRef/UNom) by kilometer for branch 1 |
| Dynawo.Types.PerUnit | R2Pu | 0.02*Dynawo.Electrical.SystemBase.SnRef/(UNom*UNom) | Line resistance in pu (base SnRef/UNom) by kilometer for branch 2 |
| Dynawo.Types.PerUnit | X2Pu | 0.27*Dynawo.Electrical.SystemBase.SnRef/(UNom*UNom) | Line reactance in pu (base SnRef/UNom) by kilometer for branch 2 |
| Dynawo.Types.PerUnit | R3Pu | 0.18*Dynawo.Electrical.SystemBase.SnRef/(UNom*UNom) | Line resistance in pu (base SnRef/UNom) by kilometer for branch 3 |
| Dynawo.Types.PerUnit | X3Pu | 0.81*Dynawo.Electrical.SystemBase.SnRef/(UNom*UNom) | Line reactance in pu (base SnRef/UNom) by kilometer for branch 3 |
| Real | L1 | 120 | Branch 1 length (in km) |
| Real | L2 | 120 | Branch 2 length (in km) |
| Real | L3 | 100 | Branch 3 length (in km) |