modelGeneratorSynchronousFourWindingsWithControl
Model of synchronous generator with four windings, a governor and a voltage regulator, for the Nordic 32 test system
Extends from GeneratorSynchronousThreeWindingsWithControl (Model of synchronous generator with three windings, a governor and a voltage regulator, for the Nordic 32 test system).
Information
The controlled generator frame functions as the regulated synchronous generator of the Nordic 32 test system.It consists of a 4 windings initialized synchronous generator, which models thermal plants. The regulating elements comprise automatic voltage regulation (AVR), exciter (EXC), overexcitation limitation (OEL), power system stabilizer (PSS) and speed control by a governor (GOV).
Parameters are automatically chosen according to a preset defined in the GeneratorParameters. Then, only initial values need to be supplied.
To add another configuration, append a new line to "genFrameParamValues", "govParamValues" and "vrParamValues" in GeneratorParameters and append a fitting name in the "genFramePreset" enumeration.
Parameters
| Type | Name | Default | Description |
|---|---|---|---|
| GeneratorWithControl.GeneratorParameters.genFramePreset | gen (from GeneratorSynchronousThreeWindingsWithControl) | Generator preset for choosing parameters and values | |
| Types.ActivePowerPu | P0Pu (from GeneratorSynchronousThreeWindingsWithControl) | Start value of active power at terminal in pu (base SnRef) (receptor convention) | |
| Types.ReactivePowerPu | Q0Pu (from GeneratorSynchronousThreeWindingsWithControl) | Start value of reactive power at terminal in pu (base SnRef) (receptor convention) | |
| Types.VoltageModulePu | U0Pu (from GeneratorSynchronousThreeWindingsWithControl) | Start value of voltage amplitude in pu (base UNom) | |
| Types.Angle | UPhase0 (from GeneratorSynchronousThreeWindingsWithControl) | Start value of voltage angle in rad |
Connectors
| Type | Name | Default | Description |
|---|---|---|---|
| Dynawo.Connectors.ACPower | terminal (from GeneratorSynchronousThreeWindingsWithControl) | Connector used to connect the generator to the grid |