modelGeneratorSynchronousFourWindingsWithControl

Model of synchronous generator with four windings, a governor and a voltage regulator, for the Nordic 32 test system
Diagram of GeneratorSynchronousFourWindingsWithControl

Extends from GeneratorSynchronousThreeWindingsWithControl (Model of synchronous generator with three windings, a governor and a voltage regulator, for the Nordic 32 test system).

Information

The controlled generator frame functions as the regulated synchronous generator of the Nordic 32 test system.
It consists of a 4 windings initialized synchronous generator, which models thermal plants. The regulating elements comprise automatic voltage regulation (AVR), exciter (EXC), overexcitation limitation (OEL), power system stabilizer (PSS) and speed control by a governor (GOV).
Parameters are automatically chosen according to a preset defined in the GeneratorParameters. Then, only initial values need to be supplied.
To add another configuration, append a new line to "genFrameParamValues", "govParamValues" and "vrParamValues" in GeneratorParameters and append a fitting name in the "genFramePreset" enumeration.

Parameters

TypeNameDefaultDescription
GeneratorWithControl.GeneratorParameters.genFramePresetgen (from GeneratorSynchronousThreeWindingsWithControl)Generator preset for choosing parameters and values
Types.ActivePowerPuP0Pu (from GeneratorSynchronousThreeWindingsWithControl)Start value of active power at terminal in pu (base SnRef) (receptor convention)
Types.ReactivePowerPuQ0Pu (from GeneratorSynchronousThreeWindingsWithControl)Start value of reactive power at terminal in pu (base SnRef) (receptor convention)
Types.VoltageModulePuU0Pu (from GeneratorSynchronousThreeWindingsWithControl)Start value of voltage amplitude in pu (base UNom)
Types.AngleUPhase0 (from GeneratorSynchronousThreeWindingsWithControl)Start value of voltage angle in rad

Connectors

TypeNameDefaultDescription
Dynawo.Connectors.ACPowerterminal (from GeneratorSynchronousThreeWindingsWithControl)Connector used to connect the generator to the grid

Components

TypeNameDefaultDescription
Dynawo.Examples.BaseClasses.InitializedGeneratorSynchronousThreeWindingsgeneratorSynchronous (from GeneratorSynchronousThreeWindingsWithControl)
Dynawo.Electrical.Controls.Machines.VoltageRegulators.Simplified.VRNordicvrNordic (from GeneratorSynchronousThreeWindingsWithControl)
Dynawo.Electrical.Controls.Machines.Governors.Simplified.GoverNordicgoverNordic (from GeneratorSynchronousThreeWindingsWithControl)