modelTwoWayTable
Extends from BaseClasses.PartialTwoWayValveKv.
Information
Two way valve with opening characteristic that is configured through a table.
The mass flow rate for the fully open valve is determined based
on the value of the parameter CvData.
For the different valve positions y ∈ [0, 1], this nominal flow rate is
scaled by the values of the parameter
flowCharacteristics.
The parameter flowCharacteristics declares a table of the form
| y | 0 | ... | 1 |
| φ | l | ... | 1 |
where l = Kv(y=0)/Kv(y=1) > 0 is the valve leakage. The first row is the valve opening, and the second row is the mass flow rate, relative to the mass flow rate of the fully open valve, under the assumption of a constant pressure difference across the valve. A suggested value for the valve leakage is l=0.0001. If l = 0, then this model will replace it with l = 10-8 for numerical reasons. For example, if a valve has Kv=0.5 [m3/h/bar1/2] and a linear opening characteristics and a valve leakage of l=0.0001, then one would set
CvData=IBPSA.Fluid.Types.CvTypes.Kv
Kv = 0.5
flowCharacteristics(y={0,1}, phi={0.0001,1})
Note, however, that IBPSA.Fluid.Actuators.Valves.TwoWayLinear provides a more efficient implementation for this simple case.
The parameter flowCharacteristics must meet the following
requirements, otherwise the model stops with an error:
-
The arrays in
flowCharacteristics.yandflowCharacteristics.phimust be strictly monotonic increasing. -
The first value must satisfy
flowCharacteristics.y[1]=0, andflowCharacteristics.phi[1]must be equal to the leakage flow rate, which must be bigger than zero. Otherwise, a default value of1E-8is used. -
The last values must satisfy
flowCharacteristics.y[end]=1andflowCharacteristics.phi[end]=1.
This model is based on the partial valve model IBPSA.Fluid.Actuators.BaseClasses.PartialTwoWayValve. Check this model for more information, such as the regularization near the origin.
For an example that specifies an opening characteristics, see IBPSA.Fluid.Actuators.Valves.Examples.TwoWayValveTable.
Parameters
| Type | Name | Default | Description |
|---|---|---|---|
| Data.Generic | flowCharacteristics | Table with flow characteristics |
Revisions
-
January 26, 2016, by Michael Wetter:
Removed equality comparison forRealin theassertstatements as this is not allowed in Modelica. -
August 12, 2014, by Michael Wetter:
Removed theendkeyword when accessing array elements, as this language construct caused an error in OpenModelica. -
April 4, 2014, by Michael Wetter:
Moved the assignment of the flow functionphito the model instantiation because in its base class, the keywordinputhas been added to the variablephi. -
March 26, 2014 by Michael Wetter:
First implementation.