modelBoundary_pT
Extends from IBPSA.Fluid.Sources.BaseClasses.PartialSource_p, IBPSA.Fluid.Sources.BaseClasses.PartialSource_T, IBPSA.Fluid.Sources.BaseClasses.PartialSource_Xi_C.
Information
Defines prescribed values for boundary conditions:
- Prescribed boundary pressure.
- Prescribed boundary temperature.
- Boundary composition (only for multi-substance or trace-substance flow).
Typical use and important parameters
If use_p_in is false (default option),
the p parameter is used as boundary pressure,
and the p_in input connector is disabled;
if use_p_in is true, then the p
parameter is ignored, and the value provided by the
input connector is used instead.
The same applies to the temperature T, composition Xi or X and trace substances C.
Options
Instead of using Xi_in (the independent composition fractions),
the advanced tab provides an option for setting all
composition fractions using X_in.
use_X_in and use_Xi_in cannot be used
at the same time.
Parameter verifyInputs can be set to true
to enable a check that verifies the validity of the used temperatures
and pressures.
This removes the corresponding overhead from the model, which is
a substantial part of the overhead of this model.
See #882
for more information.
Note, that boundary temperature, mass fractions and trace substances have only an effect if the mass flow is from the boundary into the port. If mass is flowing from the port into the boundary, the boundary definitions, with exception of boundary pressure, do not have an effect.
Revisions
-
February 2nd, 2018 by Filip Jorissen
Mademediumconditional and refactored inputs. See #882. -
April 18, 2017, by Filip Jorissen:
ChangedcheckBoundaryimplementation such that it is run as an initial equation when it depends on parameters only. See #728. -
January 26, 2016, by Michael Wetter:
Addedunitandquantityattributes. -
May 29, 2014, by Michael Wetter:
Removed undesirable annotationEvaluate=true. -
September 29, 2009, by Michael Wetter:
First implementation. Implementation is based onModelica.Fluid.