modelTwoElements

Thermal Zone with two elements for exterior and interior walls

Extends from OneElement.

Information

This model distinguishes between internal thermal masses and exterior walls. While exterior walls contribute to heat transfer to the ambient, adiabatic conditions apply to internal masses. Parameters for the internal wall element are the length of the RC-chain nInt, the vector of the capacities CInt[nInt] and the vector of the resistances RInt[nInt]. This approach allows considering the dynamic behaviour induced by internal heat storage.

The image below shows the RC-network of this model.

image

Parameters

TypeNameDefaultDescription
Interior walls
Modelica.SIunits.AreaAIntArea of interior walls
Modelica.SIunits.CoefficientOfHeatTransferalphaIntConvective coefficient of heat transfer of interior walls (indoor)
IntegernIntNumber of RC-elements of interior walls
Modelica.SIunits.ThermalResistance[nInt]RIntVector of resistances of interior walls, from port to center
Modelica.SIunits.HeatCapacity[nInt]CIntVector of heat capacities of interior walls, from port to center
BooleanindoorPortIntWallsfalseAdditional heat port at indoor surface of interior walls

Components

TypeNameDefaultDescription
Modelica.Thermal.HeatTransfer.Interfaces.HeatPort_aintWallIndoorSurfaceAuxiliary port at indoor surface of interior walls
BaseClasses.InteriorWallintWallRCRC-element for interior walls

Revisions

  • April 18, 2015, by Moritz Lauster:
    First implementation.