modelAdsolairController

Extends from IDEAS.Airflow.AHU.BaseClasses.AdsolairControllerInterface.

Parameters

TypeNameDefaultDescription
Modelica.Units.SI.Timetau60Thermal time constant at nominal flow rate

Components

TypeNameDefaultDescription
Modelica.Blocks.Sources.BooleanExpressiononAdiaExpIndirect evaporative cooling hysteresis status: on when TSet not obtained and damper is at maximum position, off when inlet temperature already satisfies set point
Modelica.Blocks.Sources.BooleanExpressiononChiExpActive chiller hystersis status: on when adia has been on for a while and temperature is still too low, off when IEH outlet temp satisfies requirements
Modelica.Blocks.MathBoolean.OnDelayonDelAdiOn delay before compressor may be activated
Modelica.Blocks.Sources.BooleanExpressionrevActReverse action
IDEAS.Airflow.AHU.BaseClasses.LimPidAdsolairdamPidPI controller for dampers
Modelica.Blocks.Math.AbsabsdTAbsolute temperature difference between inlet streams
Modelica.Blocks.Math.Addadd
Modelica.Blocks.Sources.RealExpressionyBypTopExpReal expression for connecting to output
Modelica.Blocks.Sources.RealExpressionyRecTopExpReal expression for connecting to output
Modelica.Blocks.Sources.RealExpressionrecupBotyReal expression for connecting to output
Modelica.Blocks.Sources.RealExpressionbypassBotyReal expression for connecting to output
Modelica.Blocks.Interfaces.RealOutputyBypTopControl signal of top bypass damper
Modelica.Blocks.Interfaces.RealOutputyRecTopControl signal of top IEH damper
Modelica.Blocks.Interfaces.RealOutputyRecBotControl signal of bottom IEH damper
Modelica.Blocks.Interfaces.RealOutputyBypBotControl signal of bottom bypass damper
Modelica.Blocks.Interfaces.BooleanOutputonAdiaIndirect evaporative cooling status
Modelica.Blocks.Interfaces.BooleanOutputonChiChiller status
IDEAS.Airflow.AHU.BaseClasses.LimPidAdsolairchiPidPi controller for chiller compressor
Modelica.Blocks.Interfaces.RealOutputmodModulation signal of chiller compressor
Utilities.Math.InverseXRegularizedinverseXRegularized
Modelica.Blocks.Sources.BooleanExpressiondamMaxDamper is at its limits -> next stage can be enabled
Modelica.Blocks.Continuous.FilterTFanFilFilter not integrated into temperature sensor since this leads to large time constants for low flow rates

Revisions

  • May 15, 2018, by Filip Jorissen:
    Changes for setting unique initial conditions.
  • January 26, 2018, by Filip Jorissen:
    Improved adsolair controller performance. See #751, #730, #729, #754.
  • April 24, 2017, by Filip Jorissen:
    Now extending from interface.