modelYD
IEEE 4 node test feeder model with balanced load and Y - D connection (step up)
Extends from IDEAS.Electrical.AC.ThreePhasesUnbalanced.Validation.IEEETests.Test4NodesFeeder.BaseClasses.IEEE4.
Information
IEEE 4 nodes validation test case with the following characteristics
- balanced load,
- power consumption on each phase P1,2,3 = 1800 kW
- power factor on each phase cosφ1,2,3 = 0.9
- voltage step-up transformer (VPri=12.47 kV, VSec = 24.9kV),
- Y-D transformer
Components
| Type | Name | Default | Description |
|---|---|---|---|
| Modelica.Blocks.Sources.Constant | load | ||
| IDEAS.Electrical.AC.ThreePhasesUnbalanced.Conversion.ACACTransformerStepUpYD | transformer |
Revisions
-
April 7, 2021, by Michael Wetter:
Set better start valuesloadRL(load1(v(start = {13000, 20000})))because for one component, the start value is far from a solution and if specified, Dymola 2022 beta3 fails to initialize the model.
This is for #2432. -
November 28, 2016, by Michael Wetter:
Set start value forloadRL(load1(v(each start = 15000)))which is needed for Dymola 2017 to find the correct solution.
This is for #584. -
October 9, 2014, by Marco Bonvini:
Added documentation. -
June 17, 2014, by Marco Bonvini:
Moved to Examples IEEE package. -
June 6, 2014, by Marco Bonvini:
First implementation.