modelHeatingNoControl

Ppd 12 example model without control

Extends from IDEAS.Examples.PPD12.Structure.

Information

Example model of a partially renovated terraced house in Belgium. This model adds the building heating system.

Parameters

TypeNameDefaultDescription
Realdp_26mm992*(m_flow_nominal/0.4)^2Pressure drop per m of duct with diameter of 26/20 mm for flow rate of 0.4kg/s
Realdp_20mm2871*(m_flow_nominal/0.4)^2Pressure drop per m of duct with diameter of 20/16 mm for flow rate of 0.4kg/s
Realdp_16mm11320*(m_flow_nominal/0.4)^2Pressure drop per m of duct with diameter of 16/12 mm for flow rate of 0.4kg/s
Modelica.Units.SI.MassFlowRatem_flow_nominal0.4Nominal water mass flow rate
Modelica.Units.SI.MassFlowRatem_flow_nominal_air300*1.2/3600Nominal air mass flow rate
Modelica.Units.SI.TemperatureTSet294.15Temperature set point
Modelica.Units.SI.TemperatureTSet2303.15Temperature set point

Components

TypeNameDefaultDescription
Modelica.Units.SI.Efficiencyeta{-6.017763e-11, 2.130271e-8, -3.058709e-6, 2.266453e-4, -9.048470e-3, 1.805752e-1, -4.540036e-1}*{TCorr^(6 - i) for i in 0:6}Boiler efficiency
RealTCorrmin(max(senTemRet.T - 273.15, 25), 75)Temperature within validity range of correlation
Modelica.Units.SI.PowerQGashea.Q_flow/eta
IDEAS.Fluid.HeatExchangers.Radiators.RadiatorEN442_2radGndRadiator ground floor: Superia super design 33/500/2400
IDEAS.Fluid.HeatExchangers.Radiators.RadiatorEN442_2radBed1Radiator for first bedroom: Superia super design 22/500/1400
IDEAS.Fluid.HeatExchangers.Radiators.RadiatorEN442_2radBat2Towel dryer for bathroom: Brugman ibiza 1186/600
IDEAS.Fluid.HeatExchangers.Radiators.RadiatorEN442_2radBed2Radiator for bedroom 2: Superia super design 22/500/1400
IDEAS.Fluid.HeatExchangers.Radiators.RadiatorEN442_2radBed3Radiator for bedroom 3: Superia super design 22/800/900
IDEAS.Fluid.HeatExchangers.Radiators.RadiatorEN442_2radBat1Main radiator for bathroom: Superia super design 33/500/1000
IDEAS.Fluid.Movers.FlowControlled_dppump
Fluid.HeatExchangers.PrescribedOutletheaBulex thermo master T30/35 represented using ideal heater
IDEAS.Fluid.Sources.Boundary_pTbou1
IDEAS.Fluid.FixedResistances.Junctionspl
IDEAS.Fluid.FixedResistances.Junctionspl1
IDEAS.Fluid.FixedResistances.Junctionspl2
IDEAS.Fluid.FixedResistances.Junctionspl3
IDEAS.Fluid.FixedResistances.Junctionspl4
IDEAS.Fluid.Actuators.Valves.TwoWayTRVvalBed1Thermostatic radiator valve for bedroom 1
Modelica.Thermal.HeatTransfer.Sensors.TemperatureSensorsenTemRadBed1
IDEAS.Fluid.Actuators.Valves.TwoWayTRVvalBat2Thermostatic radiator valve for towel dryer in bathroom
Modelica.Thermal.HeatTransfer.Sensors.TemperatureSensorsenTemRadBat2
IDEAS.Fluid.Actuators.Valves.TwoWayTRVvalBat1Thermostatic radiator valve for radiator in bathroom
Modelica.Thermal.HeatTransfer.Sensors.TemperatureSensorsenTemRadBat1
IDEAS.Fluid.Actuators.Valves.TwoWayTRVvalBed2Thermostatic radiator valve for radiator in bedroom 2
Modelica.Thermal.HeatTransfer.Sensors.TemperatureSensorsenTemRadBat3
IDEAS.Fluid.Actuators.Valves.TwoWayTRVvalBed3Thermostatic radiator valve for bedroom 3
Modelica.Thermal.HeatTransfer.Sensors.TemperatureSensorsenTemRadBat4
IDEAS.Fluid.Actuators.Valves.TwoWayTRVvalGndThermostatic radiator valve for radiator on ground floor
Modelica.Thermal.HeatTransfer.Sensors.TemperatureSensorsenTemGnd
Fluid.Sensors.TemperatureTwoPortsenTemRetReturn water temperature sensor

Revisions

  • October 30, 2024, by Lucas Verleyen:
    Updates according to IBPSA.
    See #1383 (and IBPSA, #1926).
  • October 26, 2018, by Filip Jorissen:
    Partial created for See #942.