modelWSIEG1
WECC Modified IEEE Type 1 Speed-Governing Model [PSSE-MODELS]
Parameters
| Type | Name | Default | Description |
|---|---|---|---|
| Real | K | 30.32 | Regulation gain [1/pu] |
| Types.Time | T_1 | 0.5 | Control time constant |
| Types.Time | T_2 | 1e-8 | Control time constant |
| Types.Time | T_3 | 0.1 | Control time constant |
| Types.TimeAging | U_o | 0.4 | Max. rate if valve opening |
| Types.TimeAging | U_c | -0.4 | Max. rate if valve closing |
| Types.PerUnit | P_MAX | 1.5 | Max. valve position |
| Types.PerUnit | P_MIN | 0 | Min. valve position |
| Types.Time | T_4 | 0.25 | HP section time constant |
| Types.PerUnit | K_1 | 0.307 | Fraction of power from high pressure turbine (upper branch) |
| Types.PerUnit | K_2 | 0 | Fraction of power from high pressure turbine (lower branch) |
| Types.Time | T_5 | 10 | Reheat plus intermediate pressure turbine time constant |
| Types.PerUnit | K_3 | 0 | Fraction of power from intermediate pressure turbine (upper branch) |
| Types.PerUnit | K_4 | 0.23 | Fraction of power from intermediate pressure turbine (lower branch) |
| Types.Time | T_6 | 0.588 | Reheater plus intermediate pressure turbine time constant (second) |
| Types.PerUnit | K_5 | 0.2315 | Fraction of power from low pressure turbine (first LP, upper branch) |
| Types.PerUnit | K_6 | 0.2315 | Fraction of power from low pressure turbine (first LP, lower branch) |
| Types.Time | T_7 | 1e-8 | Low pressure turbine time constant |
| Types.PerUnit | K_7 | 0 | Fraction of power from low pressure turbine (second LP, upper branch) |
| Types.PerUnit | K_8 | 0 | Fraction of power from low pressure turbine (second LP, lower branch) |
| Types.PerUnit | db1 | 0.0006 | Speed deadband |
| Types.PerUnit | err | 0 | Error deadband |
| Types.PerUnit | db2 | 0 | Gate valve deadband |
| Types.PerUnit | GV1 | 0 | Gate valve position 1 |
| Types.PerUnit | GV2 | 0.25 | Gate valve position 2 |
| Types.PerUnit | GV3 | 0.5 | Gate valve position 3 |
| Types.PerUnit | GV4 | 0.75 | Gate valve position 4 |
| Types.PerUnit | GV5 | 2 | Gate valve position 5 |
| Types.PerUnit | PGV1 | 0 | Mechanical power 1 |
| Types.PerUnit | PGV2 | 0.25 | Mechanical power 2 |
| Types.PerUnit | PGV3 | 0.5 | Mechanical power 3 |
| Types.PerUnit | PGV4 | 0.75 | Mechanical power 4 |
| Types.PerUnit | PGV5 | 2 | Mechanical power 5 |
| Integer | Iblock | 0 | |
| Integer | HP_LP | 1 | Turbine Output Power Selector [1(HP) or 2(LP) or 3(HP+LP)] |
Connectors
| Type | Name | Default | Description |
|---|---|---|---|
| Modelica.Blocks.Interfaces.RealInput | SPEED_HP | Machine speed deviation from nominal [pu] | |
| Modelica.Blocks.Interfaces.RealOutput | PMECH_HP | Turbine mechanical power [pu] | |
| Modelica.Blocks.Interfaces.RealOutput | PMECH_LP | Turbine mechanical power [pu] | |
| Modelica.Blocks.Interfaces.RealInput | PMECH0 |
Components
Revisions
Reference |
WECC Modified IEEE Type 1 Speed-Governing Model (PSS/E Manual) |
Last update |
2024-10-05 |
Author |
Giuseppe Laera, ALSETLab, RPI Rensselaer Polytechnic Institute |
Contact |