modelWyeDynLoad_3Ph

Variable balanced three-phase wye load
Diagram of WyeDynLoad_3Ph

Extends from ThreePhaseComponent (Partial model for inheritance of single-phase base power based on three-phase system base power.).

Information

This is a three-phase wye load model that allows the user to vary the power consumed during the simulation.

The user needs to input the active (P_a, P_b and P_c) and reactive (Q_a, Q_b and Q_c) powers consumed by each phase. Since the values come from independent parameters, the model allows the representation of unbalanced loads.

In addition, the model allows the load to be represented as constant power, or as a ZIP model. In the first approach, the load consumes the same value of active and reactive powers by each phase throughout the simulation. The latter approach allows the load to be represented as a sum of three terms: constant impedance, constant current and constant power. This means that, depending on voltage levels supplied, the load will consume different values of power.

In addition to that, the real input DynFact multiplies the power being consumed by the load. This allows the load to vary over time during the simulation. It is also important to note that DynFact multiplies all variables P_a, P_b, P_c, Q_a, Q_b and Q_c. That means that this model does not allow load variation to be performed only in selected variables.

Parameters

TypeNameDefaultDescription
Power flow data
Types.ApparentPowerS_b (from ThreePhaseComponent)SysData.S_bSystem base
Types.ApparentPowerS_p (from ThreePhaseComponent)SysData.S_b/3Phase base
Power flow
IntegerModelType00- Constant Power Model, 1- ZIP Model;
Types.ActivePowerP_a1e6Base Active power for phase A
Types.ReactivePowerQ_a0Base Reactive power for phase A
Types.ActivePowerP_b1e6Base Active power for phase B
Types.ReactivePowerQ_b0Base Reactive power for phase B
Types.ActivePowerP_c1e6Base Active power for phase C
Types.ReactivePowerQ_c0Base Reactive power for phase C
Load Parameters for ZIP Model
RealA_pa0Percentage of Constant Power Load for Phase A (%)
RealB_pa0Percentage of Constant Current Load for Phase A (%)
RealC_pa0Percentage of Constant Impedance Load for Phase A (%)
RealA_pb0Percentage of Constant Power Load for Phase B (%)
RealB_pb0Percentage of Constant Current Load for Phase B (%)
RealC_pb0Percentage of Constant Impedance Load] for Phase B (%)
RealA_pc0Percentage of Constant Power Load for Phase C (%)
RealB_pc0Percentage of Constant Current Load for Phase C (%)
RealC_pc0Percentage of Constant Impedance Load for Phase C (%)

Connectors

TypeNameDefaultDescription
Modelica.Blocks.Interfaces.RealInputDynFactLoad Curve [pu]
OpenIPSL.Interfaces.PwPinA
OpenIPSL.Interfaces.PwPinB
OpenIPSL.Interfaces.PwPinC

Components

TypeNameDefaultDescription
OpenIPSL.Electrical.SystemBaseSysData (from ThreePhaseComponent)Must add this line in all models

Contents

NameDescription
Coefficientsprotected
PowerDefinitionprotected