modelTwo_Areas_PSSE

11-bus 4-machine 2-area test system implemented with machine models from PSSE
Diagram of Two_Areas_PSSE

Extends from Modelica.Icons.Example (Icon for runnable examples).

Information

This example is composed by the 11-bus 4-machine 2-area system, where these two areas are connected via weak tie lines. This test system is ideal for studying dynamic stability, power interchange, oscillation damping, etc.

The four generation units are composed only of machines, differently from the system Two_Areas_PSSE_AVR, where excitation systems are also represented.

The system undergoes a three-phase-to-ground fault on Bus 8 at 3s, lasting for 200ms. Simulate the system for 10 seconds. Variables of interest are the ones related to inter-area modes. For example:

  • g1.gENSAL.SPEED
  • g2.gENSAL.SPEED
  • g3.gENSAL.SPEED
  • g4.gENSAL.SPEED

which are variables that represent the generator's deviation from nominal speed, in per unit. Note that generators 1 and 2 swing together, while swinging against generators 3 and 4. This is due to coherency between the area's group of generators.

Compare these results with the ones from Two_Areas_PSSE_AVR.

Parameters

TypeNameDefaultDescription
Realr0.0001
Realx0.001
Realb0.00175*0.5

Components

TypeNameDefaultDescription
Data.PF2PF_results
OpenIPSL.Electrical.Buses.Busbus1
OpenIPSL.Electrical.Buses.Busbus2
OpenIPSL.Electrical.Buses.Busbus3
OpenIPSL.Electrical.Buses.Busbus4
OpenIPSL.Electrical.Buses.Busbus5
OpenIPSL.Electrical.Buses.Busbus6
OpenIPSL.Electrical.Buses.Busbus7
OpenIPSL.Electrical.Buses.Busbus8
OpenIPSL.Electrical.Buses.Busbus9
OpenIPSL.Electrical.Buses.Busbus10
OpenIPSL.Electrical.Buses.Busbus11
TwoAreas.Groups.PSSE.No_Controls.G1g1
TwoAreas.Groups.PSSE.No_Controls.G2g2
TwoAreas.Groups.PSSE.No_Controls.G3g3
TwoAreas.Groups.PSSE.No_Controls.G4g4
OpenIPSL.Electrical.Branches.PwLineLine6_7
OpenIPSL.Electrical.Branches.PwLineLine5_6
OpenIPSL.Electrical.Branches.PwLineLine7_8_1
OpenIPSL.Electrical.Branches.PwLineLine7_8_2
OpenIPSL.Electrical.Branches.PwLineLine8_9_2
OpenIPSL.Electrical.Branches.PwLineLine8_9_1
OpenIPSL.Electrical.Branches.PwLineLine9_10
OpenIPSL.Electrical.Branches.PwLineLine10_11
OpenIPSL.Electrical.Events.PwFaultpwFault
OpenIPSL.Electrical.Loads.PSSE.LoadLoad7
OpenIPSL.Electrical.Loads.PSSE.LoadLoad9
OpenIPSL.Electrical.Branches.PwLineLine5_1
OpenIPSL.Electrical.Branches.PwLineLine5_2
OpenIPSL.Electrical.Branches.PwLineLine5_3
OpenIPSL.Electrical.Branches.PwLineLine5_4
OpenIPSL.Electrical.SystemBaseSysData